CO NFIGURAT IO N
HART- IP CO NFIGU RATION
4JNO0 0030 8 A
45
6.13
HART-IP Configuration
Click
Configuration
>
HART-IP
>
Port Configuration
in the left navigation column to show
the port configuration parameters.
Figure 21: HART-IP Configuration Screen
The options presented in this window are the following:
–
Gateway Polling Address
The operator can provide the desired gateway polling address from 0 to 63. To confirm
the change, submit the update button.
–
HART-IP Ports
The gateway allows up to four ports to be used for HART-IP communications. Each port
can be enabled and disabled using the provided checkbox.
Custom port 3 (TCP) and port 4 (UDP) are assigned to 5094 (it is the default HART-IP
port).
Custom port 1 (TCP) and port 2 (UDP) are assigned to 20004 (it is used by WDM soft-
ware).
To confirm the change, click
Submit
button.
HART-IP does not natively guarantee secure communication. Any node able to
communicate with the AWIN GW120 via HART-IP can perform unwanted changes
or misconfigurations that may disrupt the intended operation of the AWIN GW120
and the connected systems to it.
It is recommended to limit the HART-IP communication within trusted networks
and to strictly control accesses to such networks.