38
ABB i-bus
®
EIB / KNX
Commissioning
Fig. 25: Communication object “Calculation 1”
No..
Function
Object name
Data type
Flags
36
Send output value
Calculation 1
EIS variable
DPT variable
C, R, T
This communication object is used to send the result of calculation 1.
Depending on the calculation type selected, the result is sent as
1-bit value [0/1]
EIS 1
DPT
1.001
1-byte value [0...+ 255]
EIS 6
DPT
5.001
1-byte value [– 128...+ 127]
EIS 14
DPT
6.010
2-byte value [0...+ 65,535]
EIS 10
DPT
8.001
2-byte value [– 32,768...+ 32,767] EIS 10
DPT
7.001
2-byte value [EIB floating point]
EIS 5
DPT
9.001
4-byte value [IEE floating point]
EIS 9
DPT
14.000
In order to guarantee full interoperability with other EIB slaves, only a data type
should be selected for the output which is permissible for the calculated physical
size in compliance with KONNEX! (Refer to KNX manual chapter 3/7/2).
Table 7: Communication object 36 “Calculation 1”
No.
Function
Object name
Data type
Flags
37
See communication
object 36
Calculation 2
38
See communication
object 36
Calculation 3
39
See communication
object 36
Calculation 4
Table 8: Communication objects 37 to 39 – “Calculation 2, 3 and 4”
3.3.3 Calculation 1
3.3.4 Calculation 2, 3 und 4