32
ABB i-bus
®
EIB / KNX
Commissioning
Input 1
Options:
Channel A output value
Channel B output value
Channel C output value
Channel D output value
Input 2
Options:
Channel A output value
Channel B output value
Channel C output value
Channel D output value
These two parameters are used to set the operands for the comparative
calculation.
Function
Options:
Input 1 < Input 2
Input 1 > Input 2
Input 1 = Input 2
For setting the comparison functions.
Hysteresis (in x % of the output range of input 1)
Options:
1...5...100
This parameter is used to set the hysteresis band, which is dependent on
the output range of input 1.
Condition met
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
Condition not met
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
For setting the reaction as a result of the comparison.