![ABB Advant Controller 450 User Manual Download Page 199](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016199.webp)
Advant
®
Controller 450 User’s Guide
Section 2.2.15 Checklists
3BSE 002 415R701 Rev A
2-45
2.2.15.3 Supply
2.2.15.4 Lightning Protection
Table 2-7. Supply
Item
Concerning
Action
a.c. Mains
Connection in cabinet
Fuse
Connection of network:
Using of interference-
sensitive power supply
units not manufactured
by ABB
Internal distribution
Phase
(check for correct voltage)
Return
Protective earth (if distributed)
Note: There must be no breaks in the protective
earth line before the connection to the PE terminal.
In phase (phases)
No unsuppressed load on same finale circuit from
distribution box
Special isolation transformer for electronics supply
must be used
Incoming power supply (120/230 V) must be
separated from other cables by 5 cm or more
d.c.
(floating battery)
Earthing, supply
Negative pole to PE terminal of cabinet directly at
entry to cabinet.
d.c.
(earthed battery)
Connection
Via d.c./d.c. converter
Subrack supply
Max. power output
<
90% of stabilizer capacity
Table 2-8. Lightning Protection
Item
Concerning
Action
Lightning protec-
tion
Actions are compulsory for all circuits in:
Overhead lines
Cables above ground
Cables that leave the general earth line network
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...