![ABB Advant Controller 450 User Manual Download Page 180](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016180.webp)
Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-26
3BSE 002 415R701 Rev A
You must follow the main rule: Do not ground a signal at different points in the plant.
2.2.5.8 Grounding of Additional Equipment
Treat additional power supply units of different types, aimed at load/sensor supply and modems,
and so on erected in the controller or I/O cabinet, in the following way with respect to
grounding:
•
Connect the apparatus chassis (or PE terminal) to the protective ground via one of the
power distribution sockets on the power switch unit or directly to the cabinet chassis.
•
Consider application-adapted grounding of power supply 0 V. If desirable, connect the 0 V
terminal to the chassis. It is preferable that you use the protective earth screw.
2.2.5.9 Spare Conductors
Spares in field cables are to be grounded within a cabinet, in case of a CE-marked design.
2.2.6 Cable Routing in Cabinets
Cables are practically routed on either side of the cabinet depending on the final destination.
The physical item destination for an actual apparatus, and thereby the connection point, appears
in the circuit diagrams and other installation drawings enclosed at delivery.
The assigned space for cables that are entered in the floor opening is shown in
For your information, the space for the factory assembled cables is also indicated in
. Regard the latter cables and leads as sensitive to disturbances and keep them away
from cables coming from the plant. You will encounter these areas only when the system is
enlarged by additional equipment, for example, a circuit board and connection unit.
Plant cable routing within cabinets holding object oriented connection units (OOCU) diverge
somewhat. This is illustrated in
Figure 2-13. Individual Grounding of Process Signal
Connection unit
ST 3.5x9.5
(B6x9.5)
Self-tapping
screw
Cable
0 V lead
Cable duct
Mounting rail
Point of grounding
Sheet cable lug and
(used for certain cable shield connection too)
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...