ABB Advant Controller 450 Product Manual Download Page 1

Advant

®

 OCS

with Master software

Advant Controller 450
 
Version 2.3/1

Product Guide

 

3BSE 015 953R201 Rev B

 

Summary of Contents for Advant Controller 450

Page 1: ...Advant OCS with Master software Advant Controller 450 Version 2 3 1 Product Guide 3BSE 015 953R201 Rev B...

Page 2: ...s Inc USA MODBUS is a registered trademark of GOULD Electronics MOTIF and OSF are trademarks of Open Software Foundation MS DOS Microsoft Microsoft Excel and Word for Windows are registered trademarks...

Page 3: ...ing and Positioning 2 6 2 6 Switchgear Integration 2 6 2 7 Drives Integration 2 7 2 8 Variable Speed Drive Control 2 7 2 9 Communication 2 7 2 10 AdvaCommand Support 2 8 2 11 Local Operator Station Ma...

Page 4: ...n 4 10 4 8 4 Telecontrol SPA Bus 4 11 4 9 Power Supply System 4 12 4 9 1 Mains Network Types 4 12 4 9 2 Redundancy Mains Power Supply 4 12 4 9 3 Configuration Alternatives 4 13 4 10 ESD Protection 4 1...

Page 5: ...Environmental Immunities 7 1 Environmental Considerations 7 1 Chapter 8 Ordering Price List Structure 8 1 Basic Software Licenses 8 2 8 2 Assembled Delivery or Loose Part Delivery 8 2 8 3 Loose Part D...

Page 6: ...Advant Controller 450 Product Guide Table of Contents iv 3BSE 015 953R201 Rev B...

Page 7: ...dancy connected to Advant Controller 450 4 8 Figure 4 8 RCOM RCOM connected to Advant Controller 450 4 8 Figure 4 9 PROFIBUS DP connected to Advant Controller 450 4 9 Figure 4 10 LONWORKS connected to...

Page 8: ...Advant Controller 450 Product Guide Table of Contents vi 3BSE 015 953R201 Rev B...

Page 9: ...00 I O 5 5 Table 6 1 The I O limits of Advant Controller 450 6 1 Table 6 2 The max I O configuration of Advant Controller 450 6 2 Table 6 3 The Width of the Connection Units 6 3 Table 6 4 The function...

Page 10: ...us 100 8 11 Table 8 21 MasterFieldbus 8 11 Table 8 22 Details for MasterFieldbus 8 12 Table 8 23 Details for PROFIBUS DP 8 12 Table 8 24 Details for LONWORKS network interface 8 12 Table 8 25 Connecti...

Page 11: ...O 8 26 Table 8 48 Pulse Input and Positioning Sets for S100 I O 8 26 Table 8 49 Digital Input Sets for S100 I O 8 27 Table 8 50 Digital Output Sets for S100 I O 8 28 Table 8 51 Connection of Thyristo...

Page 12: ...Advant Controller 450 Product Guide Table of Contents x 3BSE 015 953R201 Rev B...

Page 13: ...as an integrated part of an Advant OCS system as well as in any other distributed control system 1 1 Product Benefits With Advant Controller 450 you will have the latest equipment concerning function...

Page 14: ...B IEEE 896 as the system bus Self configuration capabilities which make it possible to add units while the controller is in full operation Support of a wide range of central and distributed I O module...

Page 15: ...and maintenance tool on the module front Redundant CPU Optional Advant Controller 450 features redundant processor modules each containing CPU memory and switch over function While the active unit is...

Page 16: ...the actual application program The system program backup and the application program backup can not be mixed in one single program card Memory Backup Power Supply The RAM is secured against loss of po...

Page 17: ...s switched on or when voltage is recovered after a power failure At an interruption of voltage the system stores all the information necessary for restarting Whether the system is to continue operatio...

Page 18: ...designing your application with user defined PC elements you gain Significant reduction in translation time Memory saving with reuse Similar documentation in Function Chart Builder and On line Builder...

Page 19: ...fieldbus communication between the controller and the modulebus in the S800 I O station can be doubled redundancy The range of supported S800 I O modules is shown in Table 2 1 For further information...

Page 20: ...positioning axes per Advant Controller 450 can be used 2 6 Switchgear Integration Connection to the INSUM Motor Control Unit MCU is done via the LONWORKS Network Each LONWORKS channel on CI572 Communi...

Page 21: ...us For TYRAK which has a built in modem for the MasterFieldbus the following limitations apply the max no of convertors connected to the same LDB is 9 the max no of convertors connected to one Advant...

Page 22: ...porting HART and a configuration tool supported by the AMPL Control Configuration Telecontrol SPA Bus RCS protocol RP570 RP571 Master RTU protocol RP570 Slave RTU protocol IEC870 5 101 unbalanced Seco...

Page 23: ...ated and modified directly on the screen Standard VT 100 attributes such as reverse video flashing underscore and reduced intensity are supported The static part of a display is built using text strin...

Page 24: ...unctions of MasterView 320 Once the report is defined the video terminal is not required any more only the hard copy printer Printout is then activated from PC programs Thus reports can be generated a...

Page 25: ...incl self tuning adaptive control QC07 BAS41 QC07 LIB41 QC07 LIB42 PC elements for Fuzzy Control QC07 BAS41 QC07 FUZ41 QC07 OPF41 Functional units QC07 BAS41 QC07 LIB42 QC07 OPF41 AdvaCommand Position...

Page 26: ...vant Fieldbus 100 QC07 BAS41 CI522A TC512V1 TC513xx TC514xx TC515xx TC516 TC625 TC630 Advant Controller 70 110 160 S800 I O DCS 500B DCS 600 ACS 600 PROFIBUS DP QC07 BAS41 CI541V1 LONWORKS Network Int...

Page 27: ...QC07 BAS41 DSAI 133 DSAI 133A DSAX 110 DSAX 110A DSAO 120 DSAO 130 DSAO 130A HART multiplexer See S100 I O Product Guide for more information Support for DCS 500B DCS 600 ACS 600 motor drives QC07 BA...

Page 28: ...Advant Controller 450 Product Guide Chapter 2 Functional Description 2 14 3BSE 015 953R201 Rev B...

Page 29: ...eeded to solve the application task A description of the program modules and a specification of their contents is given below The Basic program module QC07 BAS41 together with the optional software be...

Page 30: ...ent Structure elements PCPGM CONTRM FUNCM MASTER SLAVEM BLOCK SEQ STEP Logic elements AND OR AND O OR A XOR INV SR SR D SR AA SR AO SR OO SR OA Arithmetic elements ADD SUB MUL DIV ADD MR1 ADD MR DIV M...

Page 31: ...ts SCALE SCALEDOS Table handling elements TBL R TBL RG TBL W TBL WG Ramp generators RAMP S1 Supervision elements ANALYSE COM STAT MasterFieldbus communication elements COM MP51 MFB OUT MFB IN COM CVI1...

Page 32: ...General user defined device controller GENBIN User defined on off controller GENCON User defined regulatory controller SEQ Sequence controller GROUP Device group controller MOTCON Motor controller VA...

Page 33: ...lso part of the following functional units which is shown in Table 3 5 Feedback control elements P DEADB P 1 INT DER PI PIP PDP CON PU1 RAMP Analog thyristor converter elements CVB I CVB O 1 The PC el...

Page 34: ...e QC07 OPF41 extends the functionality given by the Basic program module with the following functions Functional units binary1 Functional units analog1 Functional units PID loop control PIDCON1 PIDCON...

Page 35: ...built up of a combination of normal PC elements from the standard PC element libraries of the Advant Controller 450 After the user defined PC element is installed in the Advant Controller 450 it can b...

Page 36: ...Advant Controller 450 Product Guide Chapter 3 Software Components 3 8 3BSE 015 953R201 Rev B...

Page 37: ...Guide Section 4 1 Processor Module 3BSE 015 953R201 Rev B 4 1 Chapter 4 Hardware Components 4 1 Processor Module Figure 4 1 Front View of the Processor Module PM511V ABB PM 511V F RUN HLT TO BC DUAL E...

Page 38: ...ad write memory RAM PM511V08 is upgradable to PM511V16 with a special kit containing 16 Mbyte RAM Redundant Processor Modules If a failure is detected in the active unit it is halted and the backup un...

Page 39: ...ication with DB element MVB Each interface holds two lines CI534V04 Allen Bradley DF1 communication with DB element MVB Each interface holds two lines CI535V24 RCS protocol RP570 Master CI535V29 RCS p...

Page 40: ...ls RUN LIVE BAT PFAIL Four general purpose inputs 24 V One FANFAIL input One external system clock SYNC input minute pulse Two relay outputs controlled by RUN signal Processor Module A and B Part A of...

Page 41: ...ble 2 1 lists the various I O modules available for Advant Controller 450 Further information about S800 I O is given in the Product Guide for S800 I O Table 4 2 System unit for Advant Controller 450...

Page 42: ...s 300 or 300E NOTE Bus redundancy can be achieved by using two single buses 4 8 2 Fieldbus Communication Advant Fieldbus 100 using Coaxial Media Figure 4 3 MasterBus 300 300E connected to Advant Contr...

Page 43: ...pair media is shown Figure 4 5 Advant Fieldbus 100 using Twisted Pair Media connected to Advant Controller 450 Figure 4 6 Advant Fieldbus 100 using Media Redundancy connected to Advant Controller 450...

Page 44: ...required instead of 2 x TC516 and 2 x TC505 RCOM RCOM NOTE Bus redundancy can be achieved by using two single buses Figure 4 7 Advant Fieldbus 100 using Bus Redundancy connected to Advant Controller 4...

Page 45: ...can be connected to Advant OCS s PROFIBUS DP solution via the external segment couplers KFD2 BR Ex1 PA or KFD2 BR 1 PA from the company Pepperl Fuchs GmbH LONWORKS Network Interface NOTE The bus termi...

Page 46: ...8 3 External Communication EXCOM Figure 4 11 MasterFieldbus connected to Advant Controller 450 Figure 4 12 EXCOM connected to Advant Controller 450 AC 450 SC510 or SC520 CI570 TK570 Single or redundan...

Page 47: ...elecontrol SPA Bus Figure 4 13 MultiVendor Interface connected to Advant Controller 450 Figure 4 14 GCOM connected to Advant Controller 450 Figure 4 15 Telecontrol SPA Bus connected to Advant Controll...

Page 48: ...2 is capable of backing up these circuits for minimum 2 hours 4 9 1 Mains Network Types The power supply system can be connected to the following types of mains supply 120 230 V a c 50 or 60 Hz 24 48...

Page 49: ...ower supply Please see Table 4 4 for an overview Table 4 4 Different power supply arrangements for Advant Controller 450 with S100 I O Power supply Redundancy Configuration Remark No Yes 120 230 V a c...

Page 50: ...ower switch Power switch Voltage Regulator SR511 Voltage Regulator SR511 A B Load Voting unit SS110 Load Voltage Regulator DSSR 170 Voltage Regulator DSSR 170 Voltage Regulator DSSR 170 Voting unit DS...

Page 51: ...tatic electricity discharge 4 11 CE Marked Equipment In a CE marked equipment certain communication cables passing the bottom of the cabinet shall have the cable shield grounded via a capacitor The ca...

Page 52: ...Advant Controller 450 Product Guide Chapter 4 Hardware Components 4 16 3BSE 015 953R201 Rev B...

Page 53: ...es etc to be used some variations can occur Figure 5 1 shows an example of the arrangement of a controller in two cabinets NOTE Two different cabinet versions are used RM500V1 and RM500V2 Please refer...

Page 54: ...ts for the controller subrack and the five possible I O subracks that can be connected to the same electrical S100 I O bus extension An extra cabinet in the configuration figures below showed as the c...

Page 55: ...vant Controller 450 with S100 I O assembled in RM500V1 cabinets Table 5 1 RM500V1 configurations for Advant Controller 450 with S100 I O Configur ation RM500V1 cabinet No No of I O Subracks Remark A1...

Page 56: ...m are connected to the same power switch placed in the cabinet housing the controller subrack Cabinet no 1 3 and 5 have their own power supplies power switch in cabinet no 1 One set of power supplies...

Page 57: ...urations for Advant Controller 450 with S100 I O Configur ation RM500V2 cabinet No No of I O Subracks Remark B1 1 0 B2 1 1 B3 1 2 1 B4 1 3 2 Only I O 2 subrack in cabinet 3 B5 1 4 2 Only I O 2 subrack...

Page 58: ...Advant Controller 450 Product Guide Chapter 5 Mechanical Design 5 6 3BSE 015 953R201 Rev B...

Page 59: ...0 is limited as shown in Table 6 1 I O signals from other I O devices connected via for example PROFIBUS DP are not included in the table Table 6 1 The I O limits of Advant Controller 450 Channel type...

Page 60: ...boards 48 DSAI 133 2 DSAI 133A 2 DSAX 110 DSAX 110A DSDP 150 DSDP 170 DSDC 111 3 DSDP 140A 3 4 2 Only when DSAI 133 and DSAI 133A are used in redundant configuration When used in single configuration...

Page 61: ...it Width in mm inch DSTA 001A 240 9 4 DSTA 001B 240 9 4 DSTA 002A 240 9 4 DSTA 002B 240 9 4 DSTA 131 240 9 4 DSTA 133 240 9 4 DSTA 135 240 9 4 DSTA 137 470 18 5 DSTA 138 470 18 5 DSTA 145 240 9 4 DSTA...

Page 62: ...50A 240 9 4 DSTD 190 120 4 7 DSTD 190V1 120 4 7 DSTD 195 120 4 7 DSTD 196 120 4 7 DSTD 196P 120 4 7 DSTD 197 120 4 7 DSTD 198 120 4 7 DSTX 110 120 4 7 DSTX 170 240 9 4 DSTY 101 53 2 1 Table 6 4 The fu...

Page 63: ...clically transmitted to their respective destinations with a cycle time normally selectable in the range 0 5 to 64 s Cycle times can be redefined to values between 50 ms and 1000 s MVI data set and da...

Page 64: ...CPU 2 MasterBus 300 executed in slave CPU 6 Tot 6 1 MasterBus 300E executed in slave CPU 6 GCOM 5 Tot 9 RCOM RCOM 9 Multivendor Interface 9 Telecontrol SPA Bus 5 MasterFieldbus 7 Advant Fieldbus 100...

Page 65: ...ter 2 ports for EXCOM and 4 ports for MasterView 320 3 Only one CS513 on each SC520 when MasterBus 300 MasterBus 300E is executed in main CPU 4 MasterBus 300 300E in main CPU and in slave CPU can not...

Page 66: ...and S800 I O Time tagging of one DI signal on S100 I O board and one DI signal on S800 I O module The relative time error between events handled within one controller is max 3 ms The relative time err...

Page 67: ...time of reading I O signals in the Advant Controller 55 70 110 or 160 AC 70 Calculated in AMPL 2 Sct 1 RCOM RCOM AC 110 160 DI650 50 2 2 This value is valid for a fixed RCOM connection where there is...

Page 68: ...duties other than merely executing PC programs For example the processing of analog signals involves the following operations Conversion of analog input signals from transducer signals to process rela...

Page 69: ...element CON PU1 and Some arithmetic and logic PC elements 1 0 Ratio station 1 DB element AI and 1 RATIOSTN 0 4 Motor control 1 1 DB element DO and 1 MOTCON 0 4 Motor control 2 1 DB element AI 1 DB el...

Page 70: ...from data set peripheral communication can be estimated from the examples in Table 6 13 Full data set peripherals 8 DAT values are assumed However the length of the data sets has little effect on the...

Page 71: ...1 not included x 0 3 S800 I O x 0 27 DI DO signals S100 I O x 0 26 S400 I O MP 51 not included x 0 26 S800 I O x 0 14 S800 I O station No of S800 I O stations on AF 100 x 0 4 Calculated signals For pr...

Page 72: ...of Profibuses x 1 2 Number of Profibus slaves x 0 8 LONWORKS Network No of LONWORKS Communication Modules CI572 x 65 No of LONWORKS Devices x 0 2 No of LONWORKS variables input and outputs x 0 06 No...

Page 73: ...30 dynamic values 4 The figures apply to 100 events per list 5 The figures are calculated for 1 log with 10 variables each with 240 stored values Each value takes approximately 5 byte 6 The figures ar...

Page 74: ...k Table 6 16 The No of slots in the controller subrack Part No of slots Part A 8 Part B 5 Part C 5 Table 6 17 Modules that can go into part A of the controller subrack Description Consists of Max modu...

Page 75: ...e connection units for S100 I O boards Information about how many mounting bars can be used in different cabinets of RM500 type are given in Table 6 20 Table 6 19 RM500 cabinets dimensions Cabinet Ver...

Page 76: ...Advant Controller 450 Product Guide Chapter 6 Technical Data and Performance 6 18 3BSE 015 953R201 Rev B...

Page 77: ...ring operation are specified in a separate environmental data sheet Limit values are given to Corrosive gases Temperature Vibration Moisture ElectroMagnetic Compatibility etc For further information a...

Page 78: ...Advant Controller 450 Product Guide Chapter 7 Environmental Immunities 7 2 3BSE 015 953R201 Rev B...

Page 79: ...00 I O Use this price list for each physically distributed cluster of S100 I O subracks via the optical bus extension 1 5 copies of the price list can be used for the same controller S800 I O See Prod...

Page 80: ...he calculated number of I O signals is 725 the 3 licenses for 0 208 209 400 401 800 I O signals are required License for CPU redundancy This license must be ordered if the Advant Controller 450 shall...

Page 81: ...f Conformity which accompanies the loose part delivery must be signed by the person responsible for assembling the controller in cabinets 8 4 Non Standard Program Modules The item Loading of BU BA spe...

Page 82: ...1 Assembly and test of subracks 3BSE016033R1 Table 8 2 System Units Description Consists of Article No System unit to fit in RM500 cabinet with single 5 V regulator and basic program QC07 BAS41 versio...

Page 83: ...3BSE016034R1 Basic Advant Interface to LONWORKS Network license for one module 3BSE019973R1 Table 8 6 Optional Standard Program Modules Description Consists of Article No Program module containing ad...

Page 84: ...econtrol and SPA Bus Description Consists of Article No Program module for HPC563 RTU RCS and SPA server support version 3 2 latest revision YC572 3BSE022222R3 FCB description files for Telecontrol 3...

Page 85: ...BSE022168R101 Table 8 9 System software Back up Card Description Consists of Article No System software back up card SSWBUC with identical software contents as the program card for the controller syst...

Page 86: ...o Optical modem TC560V1 3BSE014164R1 Terminator TX560 3BSE005881R1 Interconnector TK560 3BSE005880R1 Connection cable 1 8m 5 9 ft for connection between PM511V or TK566 and TC560V1 TK580 3BSC950057R1...

Page 87: ...for MasterBus 300E for connection to one MasterBus 300E bus cable CS513 strapped for Mas terBus 300E 3BSE004773R1 Transceiver set for one MasterBus 300 or MasterBus 300E connection MB300K01 5730030 V...

Page 88: ...C625 or TC630 to a coaxial bus line Note BNC con nectors fit RG11 cable TK516 2 BNC connectors BNC T connector 2 red 2 blue marking rings 3BSE006251R1 Advant Fieldbus 100 termina tor kit 1x75 BNC term...

Page 89: ...R1 Cable adaptor for connection of one TC512 TC513 or TC516 to 150 ohm twisted pair cable TC501V150 TC505 3BSE009616R1 Advant Fieldbus 100 connector kit Drop cable TK516 length 40 cm 15 7 For connecti...

Page 90: ...V1 3BSE014666R1 Table 8 24 Details for LONWORKS network interface Description Consists of Article No Communication interface for LONWORKS network two channels 1250 kbit s CI572 3BSE017712R1 Table 8 25...

Page 91: ...AC 450 Used without modems up to 15 m 49 ft bus length CI532V03 3BSE003828R1 Bus controller for Allen Bradley DF1 for con nection of two buses to AC 450 Used without modems up to 15 m 49 ft bus lengt...

Page 92: ...6 25 miles 120 230 V a c DSTC X008 5751030 1 Connection cable for connection between CI53x and DSTC X008 length 3m 10 2 ft TK577 3BSE004650R1 Mounting plate for up to 2 modem units type TC512 TC513 T...

Page 93: ...ns supply SA167K03 for controller subrack and I O subrack 1 Input 120 V a c 50 60 Hz Output 24 V 25 A d c unregulated 2xSA167 2xSX554 2xSX540 2xTK402V014 TK451 3BSE003579R1 a c mains supply SA161K10 f...

Page 94: ...50 60 Hz Output 24 V 25 A d c unregulated SA168 SX554 TK402V051 3BSE008787R1 a c mains supply SA162K11 for I O subrack 4 Input 230 V a c 50 60 Hz Output 24 V 10 A d c unregulated SA162 SX554 TK402V060...

Page 95: ...s of Article No Single d c mains supply without d c d c conversion DSSB170K04 for controller subrack and I O subrack 1 Energy reservoir Capacity 3 ms at 25 A d c DSSB 170 SX555 SX557 3BSE003589R1 Sing...

Page 96: ...e 8 34 Power Supply in RM500V2 Cabinet 230V a c Mains Description Consists of Article No Single a c mains supply SA168K05 for controller subrack and I O subrack 1 Input 230 V a c 50 60 Hz Output 24 V...

Page 97: ...ed 1 SD150 SX554 SX555 3BSE004440R1 Red d c mains supply for controller subrack and I O subrack 1 Input 18 5 30 V d c Output 24 V 20 A d c regulated 1 2xSD150 2xSX554 2xSX555 TK451 3BSE004424R1 Single...

Page 98: ...ains supply without d c d c conversion DSSB170K05 for I O subrack 2 and 3 or 4 and 5 Energy reservoir Capacity 3 ms at 25 A d c DSSB 170 SX557 3BSE003590R1 Table 8 37 Extra Power Supply in RM500 Cabin...

Page 99: ...170 3BSE004443R1 Red d c power supply Input 30 60 V d c Output 24 V 20 A d c regulated 1 2xSD150 DSSS 170 2xTK582V027 3BSE003600R1 Table 8 38 Miscellaneous Power Supply Equipment in RM500 Cabinet Des...

Page 100: ...ains SB511 TK404 3BSE004451R1 Battery unit NiCd adapted for RM500 Cabinet SB522 TK460 3BSE016019R1 Table 8 40 Mains Supply Filter Description Consists of Article No Mains supply Filter 250 V a c d c 2...

Page 101: ...5 2 5 m 8 3 ft DSBC 176 DSTC 176 DSTK 227L0 1 TK575 3BSE019956R1 Connection kit for single S100 I O bus extension to I O subrack For subrack no 2 and 4 TK517V040 4 m 11 7 ft DSBC 176 DSTK 227L0 1 TK51...

Page 102: ...ed each channel separately fuse protected resolution 12 bit 0 to 10 V or 0 to 20 mA shunt 250 0 05 for 2 wire transmitters CMV 50 V CMRR 100 dB 50 Hz DSAI 130 DSTA 133 DSTK 221L3 or DSAI 130A DSTA 135...

Page 103: ...channels resolution 12 bits 0 to 10 V or 0 to 20 mA DSAO 120 DSTA 170 DSTK 223L3 3BSE019917R1 16 channels resolution 8 bits 0 to 10 V or 0 to 20 mA DSAO 130 DSTA 180 DSTK 221L3 3BSE019918R1 8 channel...

Page 104: ...ioning loop Pulse encoder input 3 ch 15mA max 80 kHz DI DO 24 V d c AO resolution 11 bits 0 to 10 V or 0 to 20 mA DSDP 140A DSTD 190 DSTK 225SL3 3BSE019921R1 Positioning Set for one positioning loop P...

Page 105: ...pulse extension time tagging with 1 ms resol Connection unit for 8 channels 24 V d c all channels galvanically isolated Connection unit for 8 channels 24 V d c 48 V d c over open input Con unit for 8...

Page 106: ...3R1 5716 0001 ABW 3BSE018335R1 3BSE018327R1 32 channels 24 V d c short circuit proof tran sistor outputs max 150 mA 32 channels 24 V d c short circuit proof tran sistor outputs max 500 mA DSDO 115 DST...

Page 107: ...V or 0 to 20 mA shunt 250 0 05 DSAI 133 2xDSTA 002A DSTK 231L5 or DSAI 133A 2xDSTA 002B DSTK 231L5 3BSE019936R1 With redundancy 32 channels resolution 12 bits single ended 0 to 10 V or 0 to 20 mA shu...

Page 108: ...Intrinsic Safety Isolator support without connection units Description Consists of Article No 16 channels resolution 12 bit differential 0 to 10 V or 0 to 20 mA shunt 250 0 1 CMV 100 V CMRR 100 dB 50...

Page 109: ...0 05 8 output channels resolution 12 bits 0 to 20 mA Cable length 10m 32 8 ft DSAX 110 DSTK 223SL10 or DSAX 110A DSTK 223SL10 3BSE019948R1 8 input channels resolution 12 bits single ended 0 to 10 V or...

Page 110: ...8 ft DSDO 115 DSTK 225SL10 or DSDO 115A DSTK 225SL10 3BSE019954R1 32 output channels 24 250 V a c d c Cable length 15m 49 2 ft DSDO 115 DSTK 225SL15 or DSDO 115A DSTK 225SL15 3BSE019955R1 Table 8 54 M...

Page 111: ...SE016055R1 Single cabinet sealed IP54 height 2125 mm 83 7 for cabinet no 1 4 6 or 7 RM503 3BSE016047R1 Single cabinet sealed IP54 height 2125 mm 83 7 for cabinet no 2 3 or 5 RM513 3BSE016056R1 Table 8...

Page 112: ...nets with H 2125 mm 83 7 3BSE016256R1 Shield plate for shielding between RM500V2 cabinets with H 2225 mm 87 6 3BSE016257R1 Locking device for one door 3BSE016258R1 Heat exchanger air air 230 V a c for...

Page 113: ...commissioning fault tracing maintenance etc 3BSE002415R701 Installation Rules User s Guide describing the installa tion rules for Advant OCS to ensure correct function in environments where disturbanc...

Page 114: ...terView 320 containing descriptions operation instructions linkages to AMPL pro grams descriptions of error messages and a table of ASCII codes 3BSE003836R0001 MasterFieldbus and S400 I O User s Guide...

Page 115: ...V02 Advant Controller 400 Series User s Guide containing a technical description instruction for installation start up design and fault tracing for MVI MODBUS in Advant Controller 410 450 3BSE000533R0...

Page 116: ...rt 1 Common Properties User s Guide giving an introduction to the concept of Functional Units in Advant OCS 3BSE003849R201 Functional Unit Part 2 AI AO DI DO User s Guide describing the func tional un...

Page 117: ...ing Terminal Diagram Forms on paper A4 and in IGES format on 3 5 diskettes 3BSE020423R101 Orderspecific Preliminary Documentation Assembly drawing Circuit diagram in IGES format List of Apparatus Inte...

Page 118: ...R1 FUZZYCON OS Process Displays Contains process displays on operator sta tion for FUZZYCON DDS Cassette 3BSE016314R1 Advant Drives Integration Product Soft ware MD 101 Contains the type circuit DRIS3...

Page 119: ......