On-Site Service Instructions
Document nbr
3AXD10000303478
ABB Oy, Drives Service
ACx580-01 R0-R5
Related to material
Department
Date
Revision
Page
ESP300
13.08.2018
F
31 (41)
© Copyright 2018 ABB Oy. All rights reserved. Specifications subject to change without notice.
2.3.3 Removing CCON-11 / CCON-23 from its assembly
mechanics
In case there is a need to remove the control board from its assembly
mechanics, operate as follows:
a. Lift the EIA/RS-485 module off, assist with a flathead screwdriver.
Remove jumpers
b. Release the locking clamps and lift the board from its assembly
plate. Pay attention to terminals and jumpers
c. Disconnect control panel cable
d. Replace CCON, connect control panel cable. Pay attention to the
connectors and jumpers when installing CCON to its assembly
mechanics
2.3.4 Removing CCON-12 from its assembly mechanics
In case there is a need to remove the control board from its
assembly mechanics, operate as follows:
a. Release the locking clamps and lift the board from its
assembly plate. Pay attention to terminals and jumpers
b. Replace CCON. Pay attention to the connectors and
jumpers when installing CCON to its assembly mechanics
2.3.5 Rigid connectors for different frame sizes
A rigid connector is attached to the CCU-11 or
CCU-23 unit but the length of the connector
varies for different frame sizes:
Ordering code
Length
Frames
3AXD50000010956
6,6 cm / 2.36’’
Old
R0-R2
3AXD50000010957
5,6 cm / 1.97’’
R3-R5
Table 1: Rigid connector sizes
New Models of the ACX580-01 use
Ordering code
Frames
3AXD50000150540
New R1, R2
5,6 cm
6,6 cm