On-Site Service Instructions
Document nbr
3AXD10000303478
ABB Oy, Drives Service
ACx580-01 R0-R5
Related to material
Department
Date
Revision
Page
ESP300
13.08.2018
F
26 (41)
© Copyright 2018 ABB Oy. All rights reserved. Specifications subject to change without notice.
2.2.17 Frame R5, Main cooling fan,
Types:
•
ACX580-01-106A-4
•
ACX580-01-088A-2
•
ACX580-01-089A-2
•
ACX580-01-114A-2
•
ACX580-01-115A-2
•
ACX580-01-078A-4
•
ACX580-01-096A-4
•
ACX580-01-041A-6
•
ACX580-01-052A-6
•
ACX580-01-062A-6
•
ACX580-01-077A-6
The main cooling fan is located at the bottom of the drive. Replace the fan as follows:
a. Remove the drive cover and gland box cover. Remove gland box to reveal main fan.
b. Pull the main fan out the drive by pressing the holding clamps. Release the fan wire from the
drive and remove the fan
c. Clean the cooling air duct and the heat sink with compressed air. See separate instructions in
section 2.1.1
d. Check that the fans blowing
direction is outwards from the
unit. Attach the fan wire to the
drive and install the new fan.
Ensure the fan operation when
the drive is powered up
Note:
In these pictures the gland
box has been removed in order to
better visibility to the pictures.
Normally this is not done.