Standard function blocks
400
Operation
The output (OUT) is the lowest input value (IN).
Inputs
The input data type and the number of inputs (2…32) are selected by the user.
Input (IN1…IN32): INT, DINT, REAL, REAL24
Outputs
Output (OUT): INT, DINT, REAL, REAL24
MUX
(10055)
Illustration
Execution time
0.70 µs
Operation
The value of an input (IN) selected by the address input (K) is stored to the output
(OUT).
If the address input is 0, negative or exceeds the number of the inputs, the output is 0.
Inputs
The input data type and number of inputs (2…32) are selected by the user.
Address input (K): DINT
Input (IN1…IN32): INT, DINT, REAL, REAL24
Outputs
Output (OUT): INT, DINT, REAL, REAL24
SEL
(10056)
Illustration
Execution time
1.53 µs
Operation
The output (OUT) is the value of the input (IN) selected by the selection input (G).
If G = 0: OUT = IN A.
If G = 1: OUT = IN B.
Inputs
The input data type is selected by the user.
Selection input (G): Boolean
Input (IN A, IN B): Boolean, INT, DINT, REAL, REAL24
Outputs
Output (OUT): Boolean, INT, DINT, REAL, REAL24
MUX
(DINT)
79
TLA1 1 msec
(1)
K
IN1
IN2
OUT
OUT(79)
SEL
(BOOL)
80
TLA1 1 msec
(1)
G
IN A
IN B
OUT
OUT(80)
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...