Standard function blocks
369
Operation
The output (Q1) is 1 if the set input (S) is 1 and the reset input (R1) is 0. The output will
retain the previous output state if the set input (S) and the reset input (R1) are 0. The
output is 0 if the reset input is 1.
Truth table:
Inputs
Set input (S): Boolean
Reset input (R1): Boolean
Outputs
Output (Q1): Boolean
RTRIG
(10031)
Illustration
Execution time
0.38 µs
Operation
The output (Q) is set to 1 when the clock input (CLK) changes from 0 to 1. The output is
set back to 0 with the next execution of the block. Otherwise the output is 0.
Note:
The output (Q) is 1 after the first execution of the block after cold restart when the
clock input (CLK) is 1. Otherwise the output is always 0 when the clock input is 1.
Inputs
Clock input (CLK): Boolean
Outputs
Output (Q): Boolean
S
R1
Q1
previous
Q1
0
0
0
0
0
0
1
1
0
1
0
0
0
1
1
0
1
0
0
1
1
0
1
1
1
1
0
0
1
1
1
0
Q
previous
is the previous cycle output value.
RTRIG
47
TLA1 1 msec
(1)
>CLK
Q
Q(47)
CLK
previous
CLK
Q
0
0
0
0
1
1
1
0
0
1
1
0
CLK
previous
is the previous cycle output value.
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...