Standard function blocks
368
Edge & bistable
FTRIG
(10030)
Illustration
Execution time
0.38 µs
Operation
The output (Q) is set to 1 when the clock input (CLK) changes from 1 to 0. The output is
set back to 0 with the next execution of the block. Otherwise the output is 0.
Inputs
Clock input (CLK): Boolean
Outputs
Output (Q): Boolean
RS
(10032)
Illustration
Execution time
0.38 µs
FTRIG
99
TLA1 1 msec
(1)
>CLK
Q
Q(99)
CLK
previous
CLK
Q
0
0
0
0
1
0
1
0
1 (for one execution cycle time, returns to 0 at the
next execution)
1
1
0
CLK
previous
is the previous cycle output value.
RS
46
TLA1 1 msec
(1)
S
R1
Q1
Q1(46)