![ABB ACSM1 Series Manual Download Page 356](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326356.webp)
Standard function blocks
356
DINT_TO_REALn_SIMP
(10022)
Illustration
Execution time
6.53 µs
Operation
The output (O) is the REAL/REAL24 equivalent of the input (I) divided by the scale input
(SCALE).
Error codes indicated at the error output (ERRC) are as follows:
Example (from DINT to REAL24):
When I = 205 and SCALE = 100, I/SCALE = 205 /100 = 2.05 and O = 2.04999.
Inputs
Input (I): DINT
Scale input (SCALE): DINT
Outputs
The output data type is selected by the user.
Output (O): REAL, REAL24
Error output (ERRC): DINT
DINT_TO_REALn_SIMP
(REAL)
86
TLA1 1 msec
(1)
I
SCALE
O
O(86)
ERRC
ERRC(86)
Error code
Description
0
No error
1001
The calculated REAL/REAL24 value exceeds the minimum value of
the selected data type range. The output is set to the minimum value.
1002
The calculated REAL/REAL24 value exceeds the maximum value of
the selected data type range. The output is set to the maximum
value.
1003
The SCALE input is 0. The output is set to 0.
1004
Incorrect SCALE input, i.e. the scale input is < 0 or is not a factor of
10.
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...