Standard function blocks
341
BITOR
(10036)
Illustration
Execution time
0.32 µs
Operation
The output (O) bit value is 1 if the corresponding bit value of any of the inputs (I1 or I2)
is 1. Otherwise the output bit value is 0.
Example:
Input
Input (I1, I2): DINT
Output
Output (O): DINT
BSET
(10037)
Illustration
Execution time
1.36 µs
Operation
The value of a selected bit (BITNR) of the input (I) is set as defined by the bit value input
(BIT). The function must be enabled by the enable input (EN).
BITNR: Bit number (0 = bit number 0, 31 = bit number 31)
If BITNR is not in the range of 0…31 (for DINT) or 0…15 (for INT) or if EN is reset to
zero, the input value is stored to the output as it is (i.e. no bit setting occurs).
Example:
EN = 1, BITNR = 3, BIT = 0
IN = 0000 0000 1111 1111
O = 0000 0000 1111 0111
Inputs
The input data type is selected by the user.
Enable input (EN): Boolean
Number of the bit (BITNR): DINT
Bit value input (BIT): Boolean
Input (I): INT, DINT
BITOR
66
TLA1 1 msec
(1)
I1
I2
O
O(66)
I1
1 1 1 0 0 0 0 0 1 1 1 0 0 1 0 1 1 1 0 1 0 0 1 1 0 0 1 1 0 1 0 1
I2
0 0 0 0 0 1 1 1 0 0 1 0 1 1 1 0 1 0 0 1 1 0 0 1 1 0 1 0 1 1 1 1
O
1 1 1 0 0 1 1 1 1 1 1 0 1 1 1 1 1 1 0 1 1 0 1 1 1 0 1 1 1 1 1 1
BSET
(DINT)
67
TLA1 1 msec
(1)
EN
BITNR
BIT
I
O
O(67)
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...