Standard function blocks
339
XOR
(10017)
Illustration
Execution time
1.24 µs (when two inputs are used) + 0.72 µs (for every additional input). When all
inputs are used, the execution time is 22.85 µs.
Operation
The output (OUT) is 1 if one of the connected inputs (IN1…IN32) is 1. Output is zero if
all the inputs have the same value.
Example:
The inputs can be inverted.
Inputs
The number of inputs (2…32) is selected by the user.
Input (IN1…IN32): Boolean
Outputs
Output (OUT): Boolean
XOR
63
TLA1 1 msec
(1)
IN1
IN2
OUT
OUT(63)
IN1
IN2
OUT
0
0
0
0
1
1
1
0
1
1
1
0