Planning the electrical installation
45
Where control cables must cross power cables make sure they are arranged at an
angle as near to 90 degrees as possible. Do not run extra cables through the drive.
The cable trays must have good electrical bonding to each other and to the
grounding electrodes. Aluminium tray systems can be used to improve local
equalizing of potential.
A diagram of the cable routing is below.
Control cable ducts
min 500 mm (20”)
Control cables
min 200 mm (8”)
min 300 mm (12”)
Supply cable
Motor cable
Drive
Braking resistor cable
min 500 mm (20”)
Motor cable
90°
90°
Supply cable
90°
230 V
24 V
24 V 230 V
Lead 24 V and 230 V control
cables in separate ducts inside
the cabinet.
Not allowed unless the 24 V
cable is insulated for 230 V or
insulated with an insulation
sleeving for 230 V.
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 0 75 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 24: ...The ACSM1 04 24...
Page 30: ...Planning the cabinet assembly 30...
Page 46: ...Planning the electrical installation 46...
Page 70: ...Maintenance 70...
Page 84: ...Technical data 84...
Page 90: ...Mains filters 90...
Page 96: ...Dimension drawings 96 Frame size A...
Page 97: ...Dimension drawings 97...
Page 98: ...Dimension drawings 98 Frame size B...
Page 99: ...Dimension drawings 99...
Page 100: ...Dimension drawings 100 Frame size C air cooled module...
Page 101: ...Dimension drawings 101...
Page 102: ...Dimension drawings 102 Frame size C for cold plate mounting...
Page 103: ...Dimension drawings 103 Frame size D air cooled module...
Page 104: ...Dimension drawings 104 Frame size D for cold plate mounting...
Page 106: ...Dimension drawings 106 Mains filters type JFI xx...
Page 108: ...Dimension drawings 108 Braking resistors type JBR xx...
Page 110: ...Dimension drawings 110...
Page 111: ......