Planning the electrical installation
43
Motor cable shield
To function as a protective conductor, the shield must have the same cross-sectional
area as a phase conductor when they are made of the same metal.
To effectively suppress radiated and conducted radio-frequency emissions, the
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminium shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape. The better and
tighter the shield, the lower the emission level and the bearing currents.
Protecting the relay output contacts and attenuating disturbances in case
of inductive loads
Inductive loads (relays, contactors, motors) cause voltage transients when switched
off.
The relay output on the drive is protected with varistors (250 V) against overvoltage
peaks. In addition, it is highly recommended to equip inductive loads with noise
attenuating circuits (varistors, RC filters [AC] or diodes [DC]) in order to minimize the
electromagnetic emissions at switch-off. If not suppressed, the disturbances may
connect capacitively or inductively to other conductors in the control cable and form
a risk of malfunction in other parts of the system.
Insulation jacket
Copper wire screen
Helix of copper tape
Cable core
Inner insulation
Summary of Contents for ACSM1-04 Series
Page 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 55 to 110 kW ...
Page 2: ......
Page 4: ......
Page 18: ...About this manual 18 ...
Page 22: ...The ACSM1 04 22 ...
Page 64: ...Electrical installation 64 ...
Page 70: ...Maintenance 70 ...
Page 82: ...Technical data 82 ...
Page 88: ...Dimension drawings 88 Drive module ...
Page 89: ...Dimension drawings 89 Drive module continued from previous page ...
Page 91: ......