Fault tracing 529
001C A nonexisting parameter or
block is used in the program.
Edit the program to correct the parameter
reference, or to use an existing block.
001D Parameter type invalid for
selected pin.
Edit the program to correct the parameter
reference.
001E Output to parameter failed
because the parameter was
write-protected.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
0023 Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
0024
002A Too many blocks.
Edit the program to reduce the number of
blocks.
Other –
Contact your local ABB representative,
quoting the auxiliary code.
64B0
Memory unit detached The memory unit was
detached when the control unit
was powered.
Switch off the power to the control unit
and reinstall the memory unit.
In case the memory unit was not actually
removed when the fault occurred, check
that the memory unit is properly inserted
into its connector and its mounting screw
is tight. Reboot the control unit (using
parameter
by cycling power. If the problem persists,
contact your local ABB representative.
64B1
Internal SSW fault
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64B2
User set fault
Loading of user parameter set
failed because
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64FF
Fault reset
Informative fault.
An active fault has been reset.
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
. Retry.
65A1
FBA A parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
65A2
FBA B parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...