504 Fault tracing
A581
Fan
Programmable warning:
Cooling fan feedback missing.
Check the setting of parameter
, bit 14.
Check the auxiliary code to identify the
fan. Code
0
denotes main fan 1. Other
codes (format XYZ): “X” specifies state
code (
1:
ID run,
2:
normal). “Y” specifies
the index of the inverter module
connected to BCU (
0…n
, always
0
for
ZCU control units). “Z” specifies the
index of the fan (
1:
Main fan 1,
2:
Main
fan 2,
3:
Main fan 3).
Note that modules are coded starting
from 0. For example, the code
101
means that Main fan 1 of module 1
(connected to BCU channel V1T/V1R)
has faulted during its ID run.
Check fan operation and connection.
Replace fan if faulty.
A582
Auxiliary fan not
running
Programmable warning:
An auxiliary cooling fan
(connected to the fan
connectors on the control unit)
is stuck or disconnected.
The auxiliary code identifies the fan (
1:
Auxiliary fan 1,
2:
Auxiliary fan 2).
Check that the auxiliary fan supervision
selection in parameter
matches the hardware.
Make sure the front cover of the drive
module is in place and tightened.
Check auxiliary fan(s) and connection(s).
Replace faulty fan.
A5A0
Safe torque off
Programmable warning:
Safe torque off function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is lost.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual and description of
parameter
(page
).
A5EA Measurement circuit
temperature
Problem with internal
temperature measurement of
the drive.
Check the auxiliary code (format XXXY
YYZZ). “Y YY” specifies through which
BCU control unit channel the fault was
received (“0 00” with a ZCU control unit).
“ZZ” specifies the location:
With control program version 2.8x and
later:
1:
U-phase IGBT,
2:
V-phase IGBT,
3:
W-phase IGBT,
4:
Power supply
board,
5:
Power unit xINT board,
6:
Brake chopper,
7:
Air inlet (TEMP3,
X10),
8:
du/dt filter (TEMP2, X7),
9:
TEMP1 (X6).
With control program version up to and
including 2.7x:
1:
U-phase IGBT,
2:
V-phase IGBT,
3:
W-phase IGBT,
4:
Power unit INT board,
5:
Brake
chopper,
6:
Air inlet,
7:
Power supply
board,
8:
du/dt filter,
FAh:
Air in temp.
A5EB PU board powerfail
Power unit power supply
failure.
Contact your local ABB representative.
A5EC PU communication
internal
Communication errors
detected between the drive
control unit and the power unit.
Check the connections between the drive
control unit and the power unit.
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...