298 Parameters
Defines the fault limit for temperature monitoring function 2.
When measured temperature 2 exceeds the limit, the drive
trips on fault
.
The unit is selected by parameter
Note:
With a PTC sensor, the unit is ohms.
130 °C,
266 °F or
4500 ohm
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
Fault limit for temperature monitoring function 2.
1 = 1 unit
Defines the warning limit for temperature monitoring function
2. When measured temperature 2 exceeds the limit, a warning
(
) is generated.
The unit is selected by parameter
Note:
With a PTC sensor, the unit is ohms.
110 °C,
230 °F or
4000 ohm
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
Warning limit for temperature monitoring function 2.
1 = 1 unit
Selects the input for parameter
.
Not selected
None.
0
AI1 actual value
Analog input AI1 on the control unit.
1
AI2 actual value
Analog input AI2 on the control unit.
2
). -
Activates FPTC-xx thermistor protection modules installed on
the control unit of the drive. Using this word, it is also possible
to suppress the warnings (but not faults) from each module.
0010 1010b
0000 0000b …
0011 1111b
FPTC-xx module configuration word.
1 = 1
Defines the ambient temperature of the motor for the motor
thermal protection model. The unit is selected by parameter
.
The motor thermal protection model estimates the motor
temperature on the basis of parameters
…
. The
motor temperature increases if it operates in the region above
the load curve, and decreases if it operates in the region
below the load curve.
WARNING!
The model cannot protect the motor if the
motor does not cool properly because of dust, dirt, etc.
20 °C or
68 °F
-60 … 100 °C or
-75 … 212 °F
Ambient temperature.
1 = 1°
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Module in slot 1
1 = Yes: Module installed in slot 1.
1
Disable slot 1 warning
1 = Yes: Warnings from the module in slot 1 suppressed.
2
Module in slot 2
1 = Yes: Module installed in slot 2.
3
Disable slot 2 warning
1 = Yes: Warnings from the module in slot 2 suppressed.
4
Module in slot 3
1 = Yes: Module installed in slot 3.
5
Disable slot 3 warning
1 = Yes: Warnings from the module in slot 3 suppressed.
6…15
Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...