Parameters 293
35
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section
(page
Displays the motor temperature as estimated by the internal
motor thermal protection model (see parameters
…
). The unit is selected by parameter
This parameter is read-only.
-
-60 … 1000
°C or °F
Estimated motor temperature.
1 = 1°
Displays the temperature received through the source defined
by parameter
. The unit is
selected by parameter
Note:
With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
Measured temperature 1.
1 = 1 unit
Displays the temperature received through the source defined
by parameter
. The unit is
selected by parameter
Note:
With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
Measured temperature 2.
1 = 1 unit
Displays the status of optional FPTC-xx thermistor protection
modules. The word can be used as the source of eg. external
events.
Note:
The “module found” bits are updated regardless of
whether the corresponding module is activated. However, the
“fault active” and “warning active” bits are not updated if the
module is not activated. Modules are activated by parameter
This parameter is read-only.
-
0000h…FFFFh
FPTC-xx status word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Module found in slot 1
1 = Yes: An FPTC-xx module has been detected in slot 1.
1
Fault active in slot 1
1 = Yes: The module in slot 1 has an active fault (
).
2
Warning active in slot 1 1 = Yes: The module in slot 1 has an active warning (
3
Module found in slot 2
1 = Yes: An FPTC-xx module has been detected in slot 2.
4
Fault active in slot 2
1 = Yes: The module in slot 2 has an active fault (
).
5
Warning active in slot 2 1 = Yes: The module in slot 2 has an active warning (
6
Module found in slot 3
1 = Yes: An FPTC-xx module has been detected in slot 3.
7
Fault active in slot 3
1 = Yes: The module in slot 3 has an active fault (
).
8
Warning active in slot 3 1 = Yes: The module in slot 3 has an active warning (
9…15 Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...