What to do
Cause
Event name /
Aux. code
Code
(hex)
Check the settings of the motor
configuration parameters in groups
98 and 99.
Nominal current is outside limits.
4
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Nominal voltage is outside limits.
5
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Mechanical nominal power is higher
than electrical active power.
6
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Nominal power not consistent with
nominal speed and torque.
7
Check that the drive is sized
correctly for the motor.
Check that all the required parameters
in group 99 have been set.
Parameters in group 99 have not been
set.
No motor
data
A6A5
Note: It is normal for this warning to
appear during the start-up and
continue until the motor data is
entered.
Set supply voltage in parameter
The supply voltage has not been
defined.
Supply
voltage
unselected
A6A6
Close the user lock by entering an
invalid pass code in parameter
The user lock is open, ie. user lock
configuration parameters
are visible.
User lock
open
A6B0
. See section
.
Confirm the new pass code by
entering the same code in
. To
A new user pass code has been
entered in parameter
but not
confirmed in
.
User pass
code not
confirmed
A6B1
cancel, close the user lock without
confirming the new code. See section
.
Check PLC programming.
The drive does not have a functionality
requested by a PLC, or requested
functionality has not been activated.
FBA A
parameter
conflict
A6D1
Check settings of parameter groups
and
.
Check PLC programming.
The drive does not have a functionality
requested by a PLC, or requested
functionality has not been activated.
FBA B
Parameter
conflict
A6D2
Check settings of parameter groups
and
.
Check the reference source selection
parameters.
A reference source is simultaneously
connected to multiple parameters
with different units.
Reference
source
parametrization
A6DA
Check the auxiliary code (format XXYY
00ZZ). “XX” and “YY” specify the two
678 Fault tracing
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...