Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = 1 s / 100 = 1 s
Cleaning deceleration time in seconds.
0.00 ... 30000.00 s
100.00% / real32
Defines the motor current reference setting used
during acceleration period of every cleaning cycle.
This helps to produce higher starting torque and assist
acceleration.
Note: For the Acceleration boost to work, parameter
81.02 Pump cleaning option sel
, bit-7 must be set to 1.
Acceleration boost
current
81.35
10 = 1% / 100 = 1%
Acceleration boost current.
0.00 ... 300.00%
Not selected / unit32
Defines source for the cleaning abort command.
The cleaning operation can be interrupted at any time
with abort command. In such case, ESP control program
will immediately switch to production mode.
Cleaning abort
source
81.40
0
Cleaning abort source is not selected.
Not selected
1
Cleaning abort source is selected.
Selected
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
See
Terms and abbreviations (page 169)
Other [bit]
Motor current % /
unit32
Defines the source for the supervision low signal.
The value from this parameter is then compared with
the limit set in parameter
If the observed signal is lower than the limit for the
time period set in parameter
, then cleaning procedure is interrupted. The ESP
control program will immediately switch to production
mode. The supervision low is not active during off-time
period.
Note: For the supervision low function to work,
parameter
81.02 Pump cleaning option sel
bit-11 must
be set to 1.
Supervision low
signal src
81.41
0
Zero
NULL
1
12.12 AI1 scaled value (page 226)
AI1 scaled
2
12.22 AI2 scaled value (page 228)
.
AI2 scaled
3
3.5 FB A reference 1 (page 179)
FBA1 ref
4
3.6 FB A reference 2 (page 179)
FBA2 ref
5
3.9 EFB reference 1 (page 179)
.
EFB1 ref
Parameters 555
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...