Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
14
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
2 x Pt1000 analog
I/O
15
As selection
, but with three
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
3 x Pt1000 analog
I/O
16
Pt1000 sensor connected to encoder interface 1. See
parameters
91.21 Module 1 temp sensor type
and
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Pt1000 encoder
module 1
17
Pt1000 sensor connected to encoder interface 2. See
parameters
91.24 Module 2 temp sensor type
and
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Pt1000 encoder
module 2
130 ° / real32
Defines the fault limit for temperature monitoring
function 2.
When measured temperature 2 exceeds the limit, the
drive trips on fault
.
The unit is selected by parameter
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 2 fault
limit
35.22
1 = 1 ° / 1 = 1 °
Fault limit for temperature monitoring function 2.
-60...1000 °
110 ° / real32
Defines the warning limit for temperature monitoring
function 2. When measured temperature 2 exceeds the
limit, a warning
(
) is generated.
The unit is selected by parameter
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 2
warning limit
35.23
1 = 1 ° / 1 = 1 °
Warning limit for temperature monitoring function 2.
-60...1000 °
Not selected / uint32
Selects the input for parameter
, selections
,
,
and
Temperature 2 AI
source
35.24
0
None.
Not selected
1
Analog input AI1 on the control unit.
AI1 actual value
2
Analog input AI2 on the control unit.
AI2 actual value
See
Terms and abbreviations (page 169)
Other [value]
0 °C / real32
Defines the calibration of temperature 2.
See parameter
35.17 Temperature 1 calibration
Temperature 2
calibration
35.27
1 = 1 °C / 1 = 1 °C
Calibration of temperature 2 in celsius.
-30...1000 °C
404 Parameters
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...