Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Start/stop/direction and run/start/jog enable signal
source selection; positive/negative reference enable
signal source selection.
Start/stop/direction
20
For information on control locations, see section
control vs. external control (page 39)
.
In1 Start; In2 Dir /
uint16
Selects the source of start, stop and direction
commands for external control location 1 (EXT1).
See also parameters
.
Ext1 commands
20.1
0
No start or stop command sources selected.
Not selected
1
The source of the start and stop commands is selected
by parameter
. The state transitions
of the source bits are interpreted as follows:
In1 Start
Command
State of source 1 (
Start
0?1 (
=
Edge)
1 (
=
Level)
Stop
0
2
The source selected by
is the start
signal; the source selected by
In1 Start; In2 Dir
determines the direction. The state transitions of the
source bits are interpreted as follows:
Command
State of source 2
State of source 1
(
)
Stop
Any
0
Start forward
0
0?1 (
=
Edge)
1 (
=
Level)
Start reverse
1
3
The source selected by
is the
forward start signal; the source selected by
In1 Start fwd; In2
Start rev
is the reverse start signal. The state
transitions of the source bits are interpreted as follows:
Command
State of source 2
State of source 1
(
)
Stop
0
0
Start forward
0
0?1 (
=
Edge)
1 (
=
Level)
Start reverse
0?1 (
=
Edge)
0
1 (
=
Level)
Stop
1
1
Parameters 279
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...