![ABB ACS880 Series Firmware Manual Download Page 187](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617187.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
0 / uint16
Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 0 of
. The event codes are listed in chapter
.
Event word 1 bit 0
code
4.41
1 = 1
Code of event.
0000…FFFFh
0000 0000h / uint32
Specifies an auxiliary code for the event selected by
the previous parameter. The selected event is indicated
by the event word only if its auxiliary code matches the
value of this parameter.
With a value of 0000 0000h, the event word will indicate
the event regardless of the auxiliary code.
Event word 1 bit 0
aux code
4.42
1 = 1
Code of warning, fault or pure event.
0000 0000h…FFFF
FFFFh
0000h / uint16
Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 1 of
. The event codes are listed in chapter
.
Event word 1 bit 1
code
4.43
1 = 1
Code of event.
0000…FFFFh
0000 0000h / uint32
Specifies an auxiliary code for the event selected by
the previous parameter. The selected event is indicated
by the event word only if its auxiliary code matches the
value of this parameter.
With a value of 0000 0000h, the event word will indicate
the event regardless of the auxiliary code.
Event word 1 bit 1
aux code
4.44
1 = 1
Code of warning, fault or pure event.
0000 0000h…FFFF
FFFFh
…
…
…
…
0000h / uint16
Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 15 of
The event codes are listed in chapter
Event word 1 bit 15
code
4.71
1 = 1
Code of event.
0000…FFFFh
0000 0000h / uint32
Specifies an auxiliary code for the event selected by
the previous parameter. The selected event is indicated
by the event word only if its auxiliary code matches the
value of this parameter.
With a value of 0000 0000h, the event word will indicate
the event regardless of the auxiliary code.
Event word 1 bit 15
aux code
4.72
1 = 1
Code of warning, fault or pure event.
0000 0000h…FFFF
FFFFh
ACS800 Standard ctrl
program / uint16
Selects whether the bit assignments of parameters
…
correspond to the ACS800 Standard control
program or the ACS800 System control program.
Fault/Warning word
compatibility
4.120
Parameters 187
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...