Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1000 = 1 mA / 1000 =
1 mA
Forced value of analog output AO1.
0.000 ... 22.000 mA
0.000 mA / real32
(Visible when
=
)
Forced value that can be used instead of the selected
output signal. See parameter
.
AO1 force data
14.78
1000 = 1 mA / 1000 =
1 mA
Forced value of analog output AO1.
0.000 ... 20.000 mA
0.100 s / real32
(Visible when
=
)
Defines the filtering time constant for analog output
AO1.
Unfiltered signal
Filtered signal
%
100
63
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
AO1 filter time
14.79
1000 = 1 s / 1000 = 1
s
Filter time constant.
0.000 ... 30.000 s
Parameters 221