96 Default control connections
PCP/ESP I/O control connections
XPOW
External power input
1
+24VI
24 V DC, 2 A
2
GND
XAI
Reference voltage and analog inputs
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Analog input 1
Speed reference
0(2)...10V,
R
in
> 200 kohm
5
AI1-
6
AI2+
Analog input 2
0(4)...20 mA,
R
in
> 100 ohm
By default, not in use.
7
AI2-
XAO
Analog outputs
1
AO1
Motor speed rpm
0...20 mA,
R
L
< 500 ohm
2
AGND
3
AO2
Motor current
0...20 mA,
R
L
< 500 ohm
4
AGND
XD2D
Drive-to-drive link
1
B
Drive-to-drive link
2
A
3
BGND
XRO1, XRO2, XRO3
Relay outputs
1
NC
Relay out 1
250 V AC / 30 VDC, 2 A
Ready run
2
COM
3
NO
1
NC
Relay output 2
250 V AC / 30 VDC, 2 A
Running
2
COM
3
NO
1
NC
Relay output 3
250 V AC / 30 VDC, 2 A
Fault (-1)
2
COM
3
NO
XD24
Digital interlock
1
DIIL
Run enable
2
+24VD
+24 V DC 200 mA
3
DICOM
Digital input ground
4
+24VD
+24 V DC 200 mA
5
DIOGND
Digital input/output ground
XDIO
Digital input/outputs
1
DIO1
Output: Ready
2
DIO2
Output: Running
XDI
Digital inputs
1
DI1
Stop (0) / Start (1)
2
DI2
By default, not in use.
3
DI3
By default, not in use.
4
DI4
By default, not in use.
5
DI5
By default, not in use.
6
DI6
By default, not in use.
XSTO
Safe torque off circuits must be closed for the drive to
start. See
Hardware manual
of drive.
X12
Safety options connection
X13
Control panel connection
X205
Memory unit connection
T
Ready run
Running
Fault (-1)
n
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...