PCP/ESP program features 47
Shutdown procedure
There are two ways to stop the drive: by coast stop or backspin control. If Backspin
control is disabled, then the drive performs normal coast stop.
Pump backspin control
Pump backspin control protects the pump during shutdown process. Backspin control
may be performed by two different function: backspin function and start delay
function.
Backspin function eliminates the effect of uncontrollable rotation of the pump in
opposite direction, that is caused by the back flow of fluid. Backspin function allows to
keep this reverse rotation below the defined speed limit. This sequence can be
performed with any stop command. User can enable this function using parameter
When zero speed is reached, the drive begins ramping to the backspin speed
reference with an acceleration time in parameter
. If the
torque in the pump is driving the motor in the reverse direction, then the actual
backspin speed is equal to the backspin speed reference. If torque in the pump is not
driving the motor in reverse, the actual speed is not equal to backspin speed
reference.
Backspin speed reference is based on actual torque.
As torque decreases, backspin speed reference increases. If torque is constant,
backspin speed range increases with the decrease in backspin speed reference.
The following procedure and time scheme describes the operation of backspin
function:
1. The Drive receives an external stop command and starts to decelerate the pump
down along the defined ramp (
).
2. At zero speed, the fluid starts flowing back from the pipe. The function keeps the
drive operational (delaying the internal stop command).
3. Backward flow accelerates the pump in reverse direction. The Backspin function
keeps the acceleration rate under the acceleration level (
4. The Backspin function keeps the reverse speed under the Backspin speed limit
) until the back flow starts running out and the
torque starts decreasing.
5. When the actual torque goes below the limit (
), the
function stops and initiates the Coast to stop command to the drive.
Backspin Speed Ref = Backspin Limit -
Max Torque
* Backspin Limit *Backspin Speed Range
Actual Torque Filtered
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...