Planning the electrical installation 57
Typical power cable sizes
CE cables
UL cables
Alternative power cable types
The power cable types that you can use with the converter are shown below.
Power cable types for limited use
Generator cables
Converter type
ACS880-87LC-
Cable
type
Conductor
type
Total quantity of parallel cables
240 mm
2
185 mm
2
120 mm
2
95 mm
2
4000A/4021A-7 EPR
Copper
9
10
13
15
4000A/4132A-7
EPR
Copper
9
10
13
15
Grid cables
Converter type
ACS880-87LC-
Cable
type
Conductor
type
Total quantity of parallel cables
240 mm
2
185 mm
2
120 mm
2
95 mm
2
4000A/4021A-7
EPR
Copper
9
11
14
16
4000A/4132A-7
EPR
Copper
9
11
14
16
Generator cables
Converter type
ACS880-87LC-
Cable
type
Conductor
type
Total quantity of parallel cables
500 kcmil
400 kcmil
350 kcmil
300 kcmil
250 kcmil
4000A/4021A-7
EPR
Copper
20
22
24
26
29
4000A/4132A-7
EPR
Copper
20
22
24
26
29
Grid cables
Converter type
ACS880-87LC-
Cable
type
Conductor
type
Total quantity of parallel cables
500 kcmil
400 kcmil
350 kcmil
300 kcmil
250 kcmil
4000A/4021A-7 EPR
Copper
21
24
26
29
32
4000A/4132A-7 EPR
Copper
21
24
26
29
32
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. The shield must meet the requirements of IEC 61800-5-1.
Check with local / state / country electrical codes for allowance.
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. A separate PE conductor is required if the shield does not
meet the requirements of IEC 61800-5-1.
Symmetrical shielded cable with three phase conductors and symmetrically
constructed PE conductor, and a shield. The PE conductor must meet the
requirements of IEC 61800-5-1.
A four-conductor system (three phase conductors and a protective conductor on
a cable tray) is not recommended for cabling.
PE
PE
PE
PE
Summary of Contents for ACS880-87LC-4000A/4021A-7
Page 4: ......
Page 10: ...10 ...
Page 17: ...Safety instructions 17 1 3 2 4 5 6 7 ...
Page 18: ...18 Safety instructions 8 9 ...
Page 28: ...28 Introduction to the manual ...
Page 52: ...52 Mechanical installation ...
Page 66: ...66 Planning the electrical installation ...
Page 74: ...74 Electrical installation Diagrams for the customer connections are presented below ...
Page 75: ...Electrical installation 75 optional Fast shutdown ...
Page 85: ...Maintenance 85 b c a Air flow direction 2 3 4 6 ...
Page 87: ...Maintenance 87 2 5 4 ...
Page 88: ...88 Maintenance 7 Arrow indicating the air flow direction 5 6 6 ...
Page 90: ...90 Maintenance Air flow circulation b a ...
Page 106: ...106 Maintenance ...
Page 124: ...124 Control units of the converter ...
Page 126: ...126 Dimension drawings ...
Page 127: ...Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...
Page 142: ...142 Cooling and heating ...