114 Technical data
Materials
Auxiliary circuit current consumption
Auxiliary circuit current consumption varies depending on the size of the converter and
selected options. For detailed information, contact your local ABB representative.
ACS880-87LC-4000A/4021A-7 and ACS880-87LC-4000A/4132A-7
UPS supply
Voltage 230 V AC ± 5%, frequency 50 Hz or 60 Hz, typical power consumption 500 W,
maximum power and current consumption 12700 W / RMS 10 ms and 55 A / RMS 10 ms
at power on, maximum power and current consumption 2000 W / RMS 20 ms and 10 A /
RMS 20 ms at start-up.
Non-UPS supply
Voltage 400 V AC ± 5%, frequency 50 Hz or 60 Hz, typical continuous power consumption
< 4500 W, maximum peak power and current consumption < 28000 W / RMS 20 ms,
maximum
I
peak
= 45 A at start-up.
Cabinet
Hot-dip zinc-coated (thickness approx. 20 µm) steel sheet (thickness 1.5 mm)
with polyester thermosetting powder coating (thickness approx. 80 µm) on
visible surfaces. Color: RAL 7035 (light beige, semi-gloss).
Color of the side panels: RAL 9017 (black, semi-gloss)
Busbars
Tin- or silver-plated copper or aluminum
Internal cooling circuit
piping
Aluminum, acid-fast stainless steel, PA pipes
Fire safety of materials
(IEC 60332-1)
Insulating materials and non-metallic items: Mostly self-extinctive
Packaging
Frame: Wood or plywood. Plastic wrapping: PE-LD. Bands: PP or steel.
Disposal
The main parts of the converter can be recycled to preserve natural
resources and energy. Product parts and materials should be dismantled and
separated.
Generally all metals, such as steel, aluminum, copper and its alloys, and
precious metals can be recycled as material. Plastics, rubber, cardboard and
other packaging material can be used in energy recovery. Printed circuit
boards and large electrolytic capacitors need selective treatment according to
IEC 62635 guidelines. To aid recycling, plastic parts are marked with an
appropriate identification code.
Please contact your local ABB distributor for further information on
environmental aspects and recycling instructions for professional recyclers.
End of life treatment must follow international and local regulations.
Summary of Contents for ACS880-87LC-4000A/4021A-7
Page 4: ......
Page 10: ...10 ...
Page 17: ...Safety instructions 17 1 3 2 4 5 6 7 ...
Page 18: ...18 Safety instructions 8 9 ...
Page 28: ...28 Introduction to the manual ...
Page 52: ...52 Mechanical installation ...
Page 66: ...66 Planning the electrical installation ...
Page 74: ...74 Electrical installation Diagrams for the customer connections are presented below ...
Page 75: ...Electrical installation 75 optional Fast shutdown ...
Page 85: ...Maintenance 85 b c a Air flow direction 2 3 4 6 ...
Page 87: ...Maintenance 87 2 5 4 ...
Page 88: ...88 Maintenance 7 Arrow indicating the air flow direction 5 6 6 ...
Page 90: ...90 Maintenance Air flow circulation b a ...
Page 106: ...106 Maintenance ...
Page 124: ...124 Control units of the converter ...
Page 126: ...126 Dimension drawings ...
Page 127: ...Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...
Page 142: ...142 Cooling and heating ...