Main circuit DC fuses
AC fuses
Converter type
ACS880-87LC-
Qty
I
N
A rms
Type
U
N
= 690 V
2×16
1400
Bussmann 170M6501
3200A/3200A-7
3AXD10000011539
■
Fuses for the voltage measurement board BAMU
The fuse type is Mersen FR14GR69V2T, 2 A; 2×3 pcs
Dimensions, weights and free space requirements
See also the dimension drawings delivered with the converter.
Weight
Dimensions
Converter type
ACS880-87LC-
Width
Depth
Height
kg (lb)
mm (in)
mm (in)
mm (in)
U
N
= 690 V
2×4700 (2×10362)
2980 (117)
1417 (56)
2436.5 (96)
3200A/3200A-7
3AXD10000011539
For free space requirements, see the dimension drawings delivered with the converter.
Losses, cooling data and noise
Noise
Cooling data
Losses
Converter type
ACS880-87LC-
Pressure
loss
Mass flow
(tolerance
-2%… +20%)
Coolant
quantity
Air
Liquid
dBA
kPa
l/min
l
kW
kW
U
N
= 690 V
< 70
120
2×300
2×52
43.8
172.7
3200A/3200A-7
3AXD10000011539
■
Internal cooling circuit data
See chapter
Terminal and lead-through data for the grid connection
Each busbar consists of two parts placed against each other. You can connect cable lugs
to both sides of the connection busbar.
Technical data 93
Summary of Contents for ACS880-87LC-3200A
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Page 48: ...48 ...
Page 68: ...68 ...
Page 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Page 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Page 108: ...108 ...
Page 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Page 116: ...116 Dimension drawings ...
Page 117: ...Dimension drawings 117 ...
Page 118: ...118 Dimension drawings ...
Page 130: ...130 ...