Default I/O diagram of the brake control unit
The diagram below shows the default I/O connections on the brake control unit, and describes
the use of the signals/connections.See also example circuit diagrams.
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 …
2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
XD2D
Drive-to-drive link
1
B
Drive-to-drive link (not in use by default)
2
A
3
BGND
4
Shield
X485
RS485 connection
5
B
Not in use (not in use by default)
6
A
7
BGND
8
Shield
XRO1…XRO3
Relay outputs
11
NC
XRO1:
Running
1)
(energized = running)
250 V AC / 30 V DC / 2 A
12
COM
13
NO
21
NC
XRO2:
Fault (-1)
1)
(energized = no fault)
250 V AC / 30 V DC / 2 A
22
COM
23
NO
31
NC
XRO3:
Running
1)
(energized = running)
250 V AC / 30 V DC / 2 A
32
COM
33
NO
XSTO
XSTO connector
1
OUT
XSTO connector. Both circuits (power module, control unit) must be closed for
the brake unit to start. (IN1 and IN2 must be connected to OUT.)
6)
2
SGND
3
IN1
4
IN2
5
IN1
Not in use
6
SGND
7
IN2
8
SGND
XDI
Digital inputs
1
DI1
Temp fault
1)
(0 = overtemperature)
2
DI2
Not in use by default
3
DI3
Not in use by default
4
DI4
Not in use by default
5
DI5
Not in use by default
6
DI6
Reset
1)
(0
ĺ
1 = fault reset)
7
DIIL
Not in use by default
XDIO
Digital input/outputs
1
DIO1
Not in use by default
2
DIO2
Not in use by default
3
DIOGND
Digital input/output ground
4
DIOGND
Digital input/output ground
XD24
Auxiliary voltage output
5
+24VD
+24 V DC 200 mA
4)
6
DICOM
Digital input ground
7
+24VD
+24 V DC 200 mA
4)
8
DIOGND
Digital input/output ground
DICOM=DIOGND
Ground selection switch
5)
XAI
Analog inputs, reference voltage output
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Not in use by default.
0(4)…20 mA,
R
in
= 100 ohm
3)
5
AI1-
6
AI2+
Not in use by default.
0(2)…10 V,
R
in
> 200 kohm
2)
7
AI2-
XAO
Analog outputs
1
AO1
Zero
1)
0…20 mA,
R
L
< 500 ohm
2
AGND
3
AO2
Zero
1)
0…20 mA,
R
L
< 500 ohm
4
AGND
XPOW
External power input
1
+24VI
24 V DC, 2.05 A
2
GND
3
+24VI
4
GND
X12
Safety functions module connection
X13
Control panel connection
X205
Memory unit connection
60 Control unit
Summary of Contents for ACS880-604
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 604 3 phase brake units as modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 34: ...Overview of kits 34 Cabinet construction ...
Page 35: ...Stage 1 Installation of common parts Cabinet construction 35 10 ...
Page 36: ...Stage 2A Installation of DC busbars 1 without DC switch or charging 36 Cabinet construction ...
Page 37: ...Stage 2B Installation of DC busbars 1 with DC switch and charging Cabinet construction 37 10 ...
Page 39: ...Stage 4 Installation of incoming resistor busbars cable connection Cabinet construction 39 10 ...
Page 40: ...Stage 5 Installation of mounting plates and cable entries 40 Cabinet construction ...
Page 41: ...Stage 6 Installation of support plate Cabinet construction 41 10 ...
Page 42: ...Stage 7 Installation of shrouding 42 Cabinet construction ...
Page 43: ...Stage 8 Installation of brake chopper module Cabinet construction 43 10 ...
Page 44: ...44 ...
Page 48: ...48 ...
Page 56: ...56 ...
Page 74: ...74 ...
Page 76: ...76 ...
Page 112: ...Frame R8i 112 Dimension drawings ...
Page 113: ...Dimension drawings 113 ...
Page 114: ...Control electronics BCU control unit 114 Dimension drawings ...
Page 123: ...Miscellaneous components Quick connector for frame R8i Dimension drawings 123 ...
Page 124: ...124 Dimension drawings ...
Page 125: ... Insertion extraction ramp for frame R8i modules Dimension drawings 125 ...
Page 126: ...126 Dimension drawings ...
Page 127: ... CRBB 4 400 188 cooling fan 218 Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...