of nuisance DC overvoltage tripping due to disturbances caused by probable high-voltage
THD in the supply voltage.
Short-circuit ratio is defined as the supply network's apparent short-circuit power
S
k,net
V
divided by the drive's nominal apparent power
S
n
.
■
Bottom cable entry/exit (oH350 and +H352)
For UL Listed (+C129) units, the default input and output cabling direction is through the
roof of the cabinet. The bottom entry (+H350) and bottom exit (+H352) options provide
power and control cable entries at the floor of the cabinet. The entries are equipped with
grommets and 360° grounding hardware.
For non-UL Listed units, bottom entry/exit is the default cabling arrangement.
■
Top cable entry/exit (oH351 and +H353)
The top entry (+H351) and top exit (+H353) options provide power and control cable entries
at the roof of the cabinet. The entries are equipped with grommets and 360° grounding
hardware.
■
Common motor terminal cubicle (H359)
As standard, each inverter module must be individually cabled to the motor. This option
provides an additional cubicle containing a single set of terminals for the motor cables.
The width of the cubicle and the size of the terminals within depend on the power rating of
the drive.
■
Thermal protection with PTC relays (oL505, +2L505, +L513,
+2L513, +L536, +L537)
PTC thermistor relay options are used for overtemperature supervision of motors equipped
with PTC sensors. When the motor temperature rises to the thermistor wake-up level, the
resistance of the sensor increases sharply. The relay detects the change and indicates
motor overtemperature through its contacts.
+L505, +2L505, +L513, +2L513
L505 provides a thermistor relay and a terminal block. The terminal block has
connections for the measuring circuit (one to three PTC sensors in series), an output
indication of the relay, and an optional external reset button. The relay can be reset either
locally or externally, or the reset circuit can be jumpered for automatic reset.
By default, the thermistor relay is wired internally to digital input DI6 of the drive control unit.
The loss of the input is set to trigger an external fault.
The output indication on the terminal block can be wired by the customer, for example, to
an external monitoring circuit. See the circuit diagrams delivered with the drive.
L513 is an ATEX-certified thermal protection function that has the same external
connectivity as +L505. In addition, +L513 comes with +Q971 (ATEX-certified safe
disconnection function) as standard and is wired at the factory to activate the Safe torque
off function of the drive in an overtemperature situation. A manual reset for the protection
function is required by Ex/ATEX regulations. For more information, see
.
O2L505 and +2L513 duplicate oL505 and +L513 respectively, containing
the relays and connections for two separate measurement circuits.
42 Operation principle and hardware description
Summary of Contents for ACS880-37LC-0390A-7
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 13: ...16 Resistor braking Further information Table of contents 13 ...
Page 14: ...14 ...
Page 24: ...24 ...
Page 28: ...28 ...
Page 50: ...50 ...
Page 70: ...70 Mechanical installation ...
Page 110: ...10 110 Electrical installation ...
Page 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Page 134: ...134 ...
Page 140: ...140 ...
Page 148: ...a b c 148 Maintenance ...
Page 151: ...4 5 6 Maintenance 151 ...
Page 164: ...164 ...
Page 174: ...174 ...
Page 196: ...196 ...
Page 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Page 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Page 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Page 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Page 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Page 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Page 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Page 210: ...Brake chopper cubicle 210 Dimensions ...
Page 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Page 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Page 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Page 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Page 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Page 238: ...238 ...
Page 240: ...240 ...