Filling up and bleeding the internal cooling circuit
Both the drive and coolant must be at room temperature before filling up the cooling circuit.
WARNING!
Make sure that the maximum permissible operating pressure is not exceeded. When
necessary regulate the pressure to appropriate level by draining excess coolant out
of the system.
WARNING!
Bleeding of the cooling circuit is very important and has to be done with great care.
Air bubbles in the cooling circuit may reduce or completely block coolant flow and
lead to overheating. Let the air out of the cooling system while filling in coolant and,
eg. after any power module replacements.
■
Drive line-ups with an ACS880-1007LC cooling unit
Obey the filling up and bleeding instructions in
ACS880-1007LC cooling unit user’s manual
.
■
Drive line-ups with a custom cooling unit
Note:
•
In filling up the system, the drain valves in the line-up are used only to vent the air from
the circuit so that it can be displaced by the coolant. The actual bleeding of the circuit
must be done via an external bleed valve installed at the highest point of the cooling
circuit. The most practical location for the valve is usually near or at the cooling unit.
•
Observe the instructions given by the manufacturer of the cooling unit. Pay special
attention to filling up and bleeding the pumps properly as they may be damaged if
operated when dry.
•
Draining coolant into the sewer system is not allowed.
1.
Open the bleed valve at the cooling unit.
2.
Open the inlet valve and the outlet-side drain valve of one cubicle. Keep the outlet valve
and the inlet-side drain valve closed.
3.
Attach a hose to the outlet-side drain valve and lead it into a suitable container.
4.
Fill the circuit with coolant. For coolant specification, see
Coolant specification (page 170)
To minimize foaming, do not exceed the filling flow rate of 5 l/min (1.3 US gallon/min).
5.
As the piping and modules in the cubicle fills up, coolant starts to flow from the hose.
Let some coolant flow out, then close the drain valve.
6.
Close the inlet valve.
7.
Repeat steps 2 to 6 for all cubicles in the line-up.
8.
Open the inlet and outlet valves in all cubicles. Let any air remaining in the system out
through the bleed valve at the cooling unit.
9.
Close the bleed valve at the cooling unit.
10. Continue to fill in coolant until a base pressure of 100…150 kPa is achieved.
11. Open the bleed valve of the pump to let out any air.
168 Internal cooling circuit
Summary of Contents for ACS880-37LC-0390A-7
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 13: ...16 Resistor braking Further information Table of contents 13 ...
Page 14: ...14 ...
Page 24: ...24 ...
Page 28: ...28 ...
Page 50: ...50 ...
Page 70: ...70 Mechanical installation ...
Page 110: ...10 110 Electrical installation ...
Page 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Page 134: ...134 ...
Page 140: ...140 ...
Page 148: ...a b c 148 Maintenance ...
Page 151: ...4 5 6 Maintenance 151 ...
Page 164: ...164 ...
Page 174: ...174 ...
Page 196: ...196 ...
Page 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Page 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Page 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Page 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Page 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Page 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Page 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Page 210: ...Brake chopper cubicle 210 Dimensions ...
Page 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Page 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Page 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Page 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Page 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Page 238: ...238 ...
Page 240: ...240 ...