Guidelines for planning the electrical installation 69
Implementing thermal overload and short-circuit
protection
Protecting the drive and input power cable in short-circuits
Protect the drive with fuses (a) and the input cable with fuses (b) or a circuit breaker as
shown below:
Size the fuses or the circuit breaker at the distribution board according to local regulations
for the input cable protection. Select the fuses for the drive according to the instructions
given in chapter
.
The fuses for the drive protection will restrict drive
damage and prevent damage to adjoining equipment in case of a short-circuit inside the
drive.
Note
: If the fuses for the drive protection are placed at the distribution board and the input
cable is dimensioned according to the nominal input current of the drive given in the rating
table on page
, the fuses will protect also the input cable in short-circuit situations,
restrict drive damage and prevent damage to adjoining equipment in case of a short-circuit
inside the drive. No separate fuses for the input cable protection are needed.
Circuit breakers
aR fuses must be used with circuit breakers.
Protecting the motor and motor cable in short-circuits
The drive protects the motor cable and motor in a short-circuit situation when the motor
cable is dimensioned according to the nominal current of the drive. No additional
protection devices are needed.
Protecting the drive and the input power and motor cables against
thermal overload
The drive protects itself and the input and motor cables against thermal overload when the
cables are dimensioned according to the nominal current of the drive. No additional
thermal protection devices are needed.
WARNING!
If the drive is connected to multiple motors, use a separate circuit
breaker or fuses for protecting each motor cable and motor against overload. The
drive overload protection is tuned for the total motor load. It may not trip due to an
overload in one motor circuit only.
Protecting the motor against thermal overload
According to regulations, the motor must be protected against thermal overload and the
current must be switched off when overload is detected. The drive includes a motor
thermal protection function that protects the motor and switches off the current when
necessary. Depending on a drive parameter value, the function either monitors a
calculated temperature value (based on a motor thermal model) or an actual temperature
~
~
M
3~
a
b
Summary of Contents for ACS880-34
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 Safety instructions ...
Page 28: ...28 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 118: ...118 External control unit ...
Page 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Page 152: ...152 Installation checklist ...
Page 156: ...156 Start up ...
Page 158: ...158 Fault tracing ...
Page 174: ...174 Maintenance ...
Page 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Page 204: ...204 Technical data ...
Page 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Page 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Page 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Page 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Page 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Page 238: ...238 Resistor braking ...
Page 242: ...242 du dt and sine filters ...
Page 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...