![ABB ACS880-34 Hardware Manual Download Page 196](http://html.mh-extra.com/html/abb/acs880-34/acs880-34_hardware-manual_2653196.webp)
196 Technical data
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a
heated, indoor, controlled environment.
Operation
installed for stationary
use
Storage
in the protective
package
Transportation
in the protective
package
Installation site altitude
For neutral-grounded
TN and TT systems and
IT (unrounded) systems:
0 to 4000 m (13123 ft)
above sea level
Above 1000 m [3281 ft]),
see page
-
-
Air temperature
-15 to +55 °C
(5 to 131 °F).
No frost
allowed. See page
.
-40 to +70 °C
(-40 to +158 °F)
-40 to +70 °C
(-40 to +158 °F)
Relative humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
Contamination levels
IEC/EN 60721-3-3:2002:
Classification of
environmental
conditions- Part 3-3:
Classification of groups
of environmental
parameters and their
severities - Stationary
use of weather protected
locations
IEC 60721-3-1:1997
IEC 60721-3-2:1997
Chemical gases
Class 3C2
Class 1C2
Class 2C2
Solid particles
Class 3S2. No
conductive dust allowed.
Class 1S3. (packing
must support this,
otherwise 1S2)
Class 2S2
Pollution degree
2
Atmospheric pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
IEC 60068-2-6:2007,
EN 60068-2-6:2008
Environmental testing Part 2-
6: Tests –Test Fc: Vibration
(sinusoidal)
Max. 0.1 mm (0.004 in.)
(10 to 57 Hz),
max. 10 m/s
2
(33 ft/s
2
)
(57 to 150 Hz) sinusoidal
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz)
sinusoidal
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
2
(49 ft/s
2
)
(9 to 200 Hz) sinusoidal
Shock
IEC 60068-2-27:2008,
EN 60068-2-27:2009
Environmental testing - Part 2-
27: Tests - Test Ea and
guidance: Shock
Not allowed
With packing max.
100 m/s
2
(330 ft./s
2
),
11 ms
With packing max.
100 m/s
2
(330 ft./s
2
),
11 ms
Free fall
Not allowed
100 mm (4 in.)
100 mm (4 in.)
Materials
Drive enclosure
• PC/ABS 2.5 mm, color NCS 1502-Y (RAL 9002 / PMS 420 C)
• hot-dip zinc coated steel sheet 1.5 to 2.5 mm, thickness of coating
100 micrometers, color NCS 1502-Y
Air baffles for RIttal cabinet
See section
.
Summary of Contents for ACS880-34
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 Safety instructions ...
Page 28: ...28 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 118: ...118 External control unit ...
Page 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Page 152: ...152 Installation checklist ...
Page 156: ...156 Start up ...
Page 158: ...158 Fault tracing ...
Page 174: ...174 Maintenance ...
Page 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Page 204: ...204 Technical data ...
Page 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Page 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Page 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Page 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Page 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Page 238: ...238 Resistor braking ...
Page 242: ...242 du dt and sine filters ...
Page 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...