Technical data 189
Derating for output voltage boosting
The drive can output a higher motor voltage than the supply voltage. This can require
derating of the drive output power depending on the difference between the supply voltage
and the output voltage to the motor for continuous operation.
This drawing shows the required derating for -3 and -5 (400 V and 500 V) drive types.
This drawing shows the required derating for -7 (690 V and 570 V) drive types.
P
N
Typical motor power in no-overload use.
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
P
Ld
Typical motor power for light-overload use.
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
*
Continuous rms output current allowing 40% overload for 1 minute every 5 minutes
U
Typical motor power in no-overload use
U
n
Nominal supply voltage of the drive. For -3 types
U
n
= 400 V, for -5 types
U
n
= 500 V. For -7
types
U
n
= 690 V but 575 V when
P
n
refers to nominal power ratings in the UL 575 V rating
tables.
P
Derated ouput power of the drive
P
n
Nominal power rating of the drive
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.10
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
P
/
P
n
U
/
U
n
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.10
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
P
/
P
n
U
/
U
n
Summary of Contents for ACS880-34
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 Safety instructions ...
Page 28: ...28 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 118: ...118 External control unit ...
Page 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Page 152: ...152 Installation checklist ...
Page 156: ...156 Start up ...
Page 158: ...158 Fault tracing ...
Page 174: ...174 Maintenance ...
Page 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Page 204: ...204 Technical data ...
Page 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Page 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Page 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Page 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Page 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Page 238: ...238 Resistor braking ...
Page 242: ...242 du dt and sine filters ...
Page 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...