Type designation keys
■
Type designation key of the supply unit
The type designation describes the composition of the unit in short. The type designation
is visible on the label (sticker) which is attached to the cabinet. The complete designation
code is divided in subcodes:
•
The first 1…18 digits form the basic code. It describes the basic construction of the unit.
The fields in the basic code are separated by hyphens.
•
The option codes follow the basic code. Each option code starts with an identifying letter
(common for the whole product series), followed by descriptive digits. The option codes
are separated by plus signs.
Basic code
Description
Code
Product series
ACS880
Default configuration: liquid-cooled cabinet-installed diode supply unit, IP42 (UL Type 1), supply
frequency 50 Hz, control (auxiliary) voltage 230 V AC, half-controlled diode thyristor bridge, IEC
industrial cabinet construction, main switch type: air circuit breaker, degree of protection IP42 (UL
type 1), EMC filter (category 3, 2nd Environment), EN/IEC approved components, speed-controlled
module cooling fans, DC busbar material copper, cable supply conductors, standard wiring material,
power and control cabling through the bottom of the cabinet, ACS-AP-W assistant control panel,
ACS880 diode supply control program, coated circuit boards, lead-through-type cable entries,
multilingual door device label sticker, complete documentation in English in a USB memory stick.
307LC
Size
Refer to the rating table in the technical data.
xxxxx
Voltage range
525…690 V. This is indicated in the type designation label as typical input voltage levels
3~525/600/690 V AC.
7
Option codes
Description
Code
12-pulse supply connection
A004
50 Hz supply frequency
A012
60 Hz supply frequency
A013
Half-controlled diode-thyristor bridge
A018
IP42 (UL Type 1)
B054
IP54 (UL Type 12)
B055
Marine construction
C121
UL Listed (evaluated to both U.S. and Canadian safety requirements)
C129
Marine type approval. Refer to
C132 marine type-approved cabinet-built drives supplement
(3AXD50000039629 [English]).
C132
Plinth height 100 mm
C164
Door hinges on left
C176
Plinth height 200 mm
C179
Marine product certification issued by DNV GL
C205
Marine product certification issued by the American Bureau of Shipping (ABS)
C206
Marine product certification issued by Lloyd's Register (LR)
C207
30 Operation principle and hardware description
Summary of Contents for ACS880-307LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 307LC diode supply units Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 34: ...34 ...
Page 41: ...10 9 7 6 8 Electrical installation 41 11 ...
Page 73: ...11 12 12 6 10 Maintenance 73 ...
Page 78: ...78 ...
Page 88: ...88 ...
Page 96: ... 400 mm wide input cubicle 96 Technical data ...
Page 97: ... 600 mm wide incoming cubicle or input cubicle Technical data 97 ...