The diagram below shows the typical current THD at nominal current in relation to
supply transformer impedance in a 6-pulse connection.
50%
45%
40%
35%
30%
25%
20%
4%
5%
%
8
%
7
%
6
Supply transformer reactance
Current THD
Selecting the power cables
■
Input AC cabling
The input AC cabling has to be identical (length and cross-sectional area) between all
the parallel-connected supply modules. Each module must have its own shielded
3-conductor input AC cable with the minimum length of 5 m (16.4 ft). This ensures
uniform loading of all the three input phases. If 1 phase cabling or shorter cables than
5 m (16.4 ft) are used to connect the supply modules to the grid, it is required to install
a separate 3-phase AC choke between each ACS880-304LC +A019 module and grid to
ensure current balance between the phases. Separate chokes are not available from
ABB.
Symmetrical shielded cable with three phase conductors and a concentric
PE conductor as shield. The shield must agree with the requirements of
IEC 61800-5-1. Check with local / state / country electrical codes for al-
lowance.
PE
Symmetrical shielded cable with three phase conductors and symmet-
rically constructed PE conductor, and a shield. The PE conductor must
agree with the requirements of IEC 61800-5-1.
PE
Symmetrical shielded cable with three phase conductors and a concentric
PE conductor as shield. A separate PE conductor is required if the shield
does not agree with the requirements of IEC 61800-5-1.
PE
60 Electrical installation
Summary of Contents for ACS880-304LC Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 30: ...30 ...
Page 34: ...34 ...
Page 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Page 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Page 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Page 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Page 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Page 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Page 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Page 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Page 54: ...54 ...
Page 74: ...74 ...
Page 87: ...5 Maintenance 87 ...
Page 88: ...6 7 8 9 9 88 Maintenance ...
Page 92: ...92 ...
Page 108: ...108 ...
Page 118: ...118 ...
Page 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Page 142: ...ZCU 14 control unit 142 Dimension drawings ...
Page 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Page 144: ...CIO 01 module 144 Dimension drawings ...
Page 152: ...152 ...