Internal cooling circuit
Contents of this chapter
The cooling system of a liquid-cooled drive consists of two circuits: the internal cooling
circuit and the external cooling circuit. The internal cooling circuit covers the
heat-generating electrical components of the drive and transfers the heat to the
cooling unit. In the cooling unit, the heat is transferred to the external cooling circuit
which is usually part of a larger external cooling system. This chapter deals with the
internal cooling circuit.
Applicability
The information in this chapter is applicable to cabinet-built ACS880 liquid-cooled
drives. Except where otherwise indicated, the information is also applicable to drives
built out of ACS880 liquid-cooled multidrives modules.
Internal cooling system
Each cubicle has an inlet and an outlet manifold, fitted with a stop valve and a drain
valve. The stop valves can be closed to isolate all modules in the cubicle from the main
cooling circuit.
In cabinet line-ups built by ABB, valves are color-coded:
•
Blue – Open during operation
•
Red – Closed during operation
The following diagram shows the coolant pipe connections in a drive system consisting
of a supply unit and an inverter unit. Other units, such as brake units, DC/DC converter
units have similar cooling arrangements. Other cubicles containing components that
require cooling may also contain heat exchangers.
10
Internal cooling circuit 109
Summary of Contents for ACS880-304LC Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 30: ...30 ...
Page 34: ...34 ...
Page 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Page 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Page 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Page 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Page 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Page 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Page 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Page 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Page 54: ...54 ...
Page 74: ...74 ...
Page 87: ...5 Maintenance 87 ...
Page 88: ...6 7 8 9 9 88 Maintenance ...
Page 92: ...92 ...
Page 108: ...108 ...
Page 118: ...118 ...
Page 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Page 142: ...ZCU 14 control unit 142 Dimension drawings ...
Page 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Page 144: ...CIO 01 module 144 Dimension drawings ...
Page 152: ...152 ...