Checking the settings of the cooling fan transformer
Check the tap settings of all cooling fan transformers. Cooling fan transformers T115 and
T125 are present depending on drive configuration. If the delivery contains an incoming
unit, the cooling fan transformer connections are made at the factory. The connection of
the primary winding of the fan transformer depends on the actual system voltage.
The voltage settings of cooling fan transformers T115 and T125 are made at terminal blocks
T115_X1/X2 and T125_X1/X2 respectively.
■
T115 and T125 tap settings (690 V units)
690 V
1
660 V
2
600 V
3
575 V
4
540 V
5
525 V
6
7
U1
8
TP1
9
TP2
10
T
115
_X1
T1
25
_X1
T
115
_X2
T1
25
_X2
1
230 V
2
3
4
N
5
Ĭ
44 Electrical installation