Option description and instructions 29
Circuit diagram
This diagram is an example circuit diagram without the safety encoder interface. For more
information, see the circuit diagrams of the delivery.
Initial status: The drive is in operation and the motor is running.
Step
Operation
1.
The user activates the emergency stop function by pushing the emergency stop button [S61]. This
activates the safety function in the FSO module.
2.
The drive decelerates/coasts the motor to zero speed using the user-defined stop category (0 or 1).
The STO circuit in the drive/inverter unit is opened.
3.
The emergency stop indication lamp [P62] illuminates as described in section
on page
.
4.
Normal operation resumes after the user:
• releases the emergency stop button [S61] to normal (up) position
• resets emergency stop circuit by pushing the emergency stop reset button [S62]
• switches the external start signal of drive off and on (only in external control mode)
• resets the drive if a fault is generated (see FSO parameter
and drive parameter
31.22 STO indication run/stop
on page
).
-S62
-A68
-S61
-A41
M
3~
1
10
9
8
7
6
5
4
3
2
DO
GND
DI
-X114
-X113
1)
TP
-P62
1)
STO signal to the drive/inverter IGBT
A41
Control board of the drive/inverter unit
A68
FSO safety functions module
X113
Terminal block in the FSO module
X114
Terminal block in the FSO module
P62
Emergency stop indication lamp
S61
Emergency stop button
S62
Emergency stop reset button
Drive module interface
Drive module
Main circuit
Summary of Contents for ACS880-17
Page 4: ......
Page 7: ...7 Document library on the Internet 57...
Page 8: ...8...
Page 34: ...34 Option description and instructions...
Page 48: ...48 Start up and acceptance test...
Page 56: ...56 Technical data...
Page 58: ...3AUA0000145921 Rev E EN 2018 02 02 Contact us www abb com drives www abb com drivespartners...