US
2)
IEC
1)
Al cable type
Cu cable type
Al cable type
Cu cable type
ACS880-
14-…
AWG/kcmil
AWG/kcmil
mm
2
mm
2
U
n
= 400 V
350 MCM or 2 × 2/0
250 MCM or 2 × 1
2 × (3 × 95)
2 × (3 × 50)
246A-3
500 MCM or 2 × 3/0
350 MCM or 2 × 2/0
2 × (3 × 120)
2 × (3 × 70)
293A-3
700 MCM or 2 × 4/0 or 3 × 2/0
500 MCM or 2 × 3/0
3 × (3 × 95)
3 × (3 × 50)
363A-3
2 × 300 MCM or 3 × 3/0
700 MCM or 2 × 4/0 or 3 × 2/0
3 × (3 × 120)
3 × (3 × 70)
442A-3
2 × 300 MCM or 3 × 3/0
700 MCM or 2 × 4/0 or 3 × 2/0
3 × (3 × 120)
3 × (3 × 70)
505A-3
2 × 500 MCM or 3 × 250 MCM
2 × 350 MCM or 3 × 4/0
3 × (3 × 150)
3 × (3 × 120)
585A-3
2 × 600 MCM or 3 × 300 MCM
2 × 400 MCM or 3 × 4/0
3 × (3 × 185)
3 × (3 × 120)
650A-3
U
n
= 500 V
250 MCM or 2 × 1
3/0
2 × (3 × 70)
1 × (3 × 120)
240A-5
350 MCM or 2 × 2/0
250 MCM or 2 × 1
3 × (3 × 70)
2 × (3 × 50)
260A-5
500 MCM or 2 × 3/0
300 MCM or 2 × 1/0
3 × (3 × 70)
2 × (3 × 70)
302A-5
500 MCM or 2 × 3/0
350 MCM or 2 × 2/0
3 × (3 × 70)
2 × (3 × 120)
361A-5
700 MCM or 2 × 4/0 or 3 × 2/0
500 MCM or 2 × 3/0
2 × (3 × 150)
3 × (3 × 50)
414A-5
2 × 300 MCM or 3 × 3/0
700 MCM or 2 × 4/0 or 3 × 2/0
3 × (3 × 120)
3 × (3 × 70)
460A-5
2 × 400 MCM or 3 × 4/0
2 × 250 MCM or 3 × 2/0
3 × (3 × 120)
3 × (3 × 95)
503A-5
U
n
= 690 V
3/0
1/0
2 × (3 × 50)
1 × (3 × 70)
142A-7
4/0
2/0
2 × (3 × 50)
2 × (3 × 50)
174A-7
300 MCM or 2 × 1/0
4/0
2 × (3 × 70)
2 × (3 × 50)
210A-7
400 MCM or 2 × 2/0
300 MCM or 2 × 1/0
3 × (3 × 50)
2 × (3 × 70)
271A-7
600 MCM or 2 × 4/0 or 3 × 1/0
400 MCM or 2 × 2/0
2 × (3 × 120)
2 × (3 × 50)
330A-7
700 MCM or 2 × 4/0 or 3 × 2/0
500 MCM or 2 × 3/0
2 × (3 × 150)
3 × (3 × 70)
370A-7
2 × 300 MCM or 3 × 3/0
700 MCM or 2 × 4/0 or 3 × 2/0
2 × (3 × 185)
3 × (3 × 70)
430A-7
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top of the
other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and IEC
60364-5-52). For other conditions, dimension the cables according to local safety regulations, appropriate input voltage
and the load current of the drive.
2) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F) ambient
temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate input voltage and the load current of
the drive.
Terminal and entry data for the power cables
Terminal and entry data for the power cables
4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG)
Maximum accepted cable
size
M12
Screw size for connecting
busbars to the drive mod-
ule input and output bus-
bars
50…75 N·m (37…55 lbf·ft)
Tightening torque
Technical data 191
Summary of Contents for ACS880-14
Page 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 14: ...14...
Page 24: ...24...
Page 30: ...30...
Page 54: ...54...
Page 64: ...64...
Page 98: ...98...
Page 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Page 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Page 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Page 150: ...150 Installation example with full cabling panels option H381...
Page 156: ...156...
Page 204: ...Standard configuration 204 Dimension drawings...
Page 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Page 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Page 208: ...LCL filter module 208 Dimension drawings...
Page 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Page 230: ...Declaration of conformity 230 The Safe torque off function...
Page 241: ...241...
Page 246: ...246...