Push the LCL filter module carefully into the enclosure along the extraction/installation ramp. Work
preferably with help from another person as shown below. Keep a constant pressure with one foot
on the base of the module to prevent the module from falling on its back.
12
Unfasten the extraction/installation ramp and attach the LCL filter module to bottom plate.
13
Drive module
Attach the extraction/installation ramp to the drive module pedestal guide plate.
14
Remove the sheeting from the clear plastic shrouds of the drive module from both sides.
15
Install the top metallic shroud to the drive module.
16
Install the back shrouds to the drive module.
17
To prevent the drive module from falling, attach its lifting lugs with chains to the enclosure frame.
18
Push the drive module carefully into the enclosure along the extraction/installation ramp. Work
preferably with help from another person as shown above. Keep a constant pressure with one foot
on the base of the module to prevent the module from falling on its back.
19
Unfasten the extraction/installation ramp and attach the drive module to the bottom plate.
20
LCL filter module and drive module attachments and intermediate electrical connections
Attach the LCL filter module and drive module to the punched section.
21
Attach the LCL filter module to the side of drive module from top. Reinstall the cover.
22
Attach the drive module and LCL filter module to the bottom plate.
23
Connect the LCL filter busbars to the drive module busbars with the connecting busbars.
24
Attach the LCL filter module to the drive module side from bottom.
25
Connect the LCL filter fan power supply cable to connector FAN3:LCL.
26
Air baffles
After the electrical installation has been done, install the air baffles. For instructions, see section
Installing the air baffles (page 136)
.
-
Connecting the motor cables and installing the shrouds
See
Connecting the motor cables and installing the shrouds (page 240)
Tasks (motor cables)
Step
Install the grounding terminal to the drive module base.
1
Run the motor cables to the enclosure. Ground the cable shields 360 degrees at the enclosure
entry.
2
134 Installation example of the standard drive module configuration in Rittal VX25 enclosure
Summary of Contents for ACS880-14
Page 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 14: ...14...
Page 24: ...24...
Page 30: ...30...
Page 54: ...54...
Page 64: ...64...
Page 98: ...98...
Page 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Page 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Page 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Page 150: ...150 Installation example with full cabling panels option H381...
Page 156: ...156...
Page 204: ...Standard configuration 204 Dimension drawings...
Page 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Page 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Page 208: ...LCL filter module 208 Dimension drawings...
Page 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Page 230: ...Declaration of conformity 230 The Safe torque off function...
Page 241: ...241...