Connecting the control cables to the terminals of the
external control unit
1. Route the cables to the control unit as shown below.
2. Ground the shields of the control cables at the clamp plate. Use torque 1.5 N·m (13 lbf·in).
The shields should be continuous as close to the terminals of the control unit as possible.
Only remove the outer jacket of the cable at the cable clamp so that the clamp presses
on the bare shield. The shield (especially in case of multiple shields) can also be
terminated with a lug and fastened with a screw at the clamp plate. Leave the other end
of the shield unconnected or ground it indirectly via a few nanofarads high-frequency
capacitor eg, 3.3 nF / 630 V. The shield can also be grounded directly at both ends if
they are in the same ground line with no significant voltage drop between the end points.
Tighten the screws to secure the connection.
3. Connect the conductors to the appropriate detachable terminals of the control unit. See
the default I/O diagram. Use shrink tubing or insulating tape to contain any strain strands.
Note:
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting
the wire with its return wire reduces disturbances caused by inductive coupling. Keep
the shields continuous as close to the terminals of the control unit as possible.
Connecting a control panel
With control panel door mounting platform, connect the control panel as follows:
1. Connect an Ethernet cable to the RJ-45 connector of the control panel.
2. Connect the other end of the cable to the X13 connector of the control unit.
112 Electrical installation
Summary of Contents for ACS880-14
Page 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 14: ...14...
Page 24: ...24...
Page 30: ...30...
Page 54: ...54...
Page 64: ...64...
Page 98: ...98...
Page 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Page 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Page 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Page 150: ...150 Installation example with full cabling panels option H381...
Page 156: ...156...
Page 204: ...Standard configuration 204 Dimension drawings...
Page 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Page 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Page 208: ...LCL filter module 208 Dimension drawings...
Page 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Page 230: ...Declaration of conformity 230 The Safe torque off function...
Page 241: ...241...
Page 246: ...246...