Connecting motor temperature sensor to the drive via an option module
This table shows:
• option module types that you can use for the motor temperature sensor connection
• insulation or isolation level that each option module forms between its temperature
sensor connector and other connectors
• temperature sensor types that you can connect to each option module
• temperature sensor insulation requirement in order to form, together with the
insulation of the option module, a reinforced insulation between the motor live parts
and the drive control unit.
Temperature sensor insula-
tion requirement
Temperature
sensor type
Option module
Pt100,
Pt1000
KTY
PTC
Insulation/Isolation
Type
Reinforced insulation
x
x
-
Galvanic isolation between
sensor connector and other
connectors (including drive
control unit connector)
FIO-11
Reinforced insulation
-
x
x
Galvanic isolation between
sensor connector and other
connectors (including drive
control unit connector)
FEN-xx
Basic insulation. Connectors of
option module other than
sensor connector must be left
unconnected.
x
x
x
Basic insulation between
sensor connector and drive
control unit connector. No insu-
lation between sensor connect-
or and other I/O connectors.
FAIO-
01
No special requirement
-
-
x
Reinforced insulation between
sensor connector and other
connectors (including drive
control unit connector).
FPTC-
xx
1)
1) Suitable for use in safety functions (SIL2 / PL c rated).
Protecting the drive against ground faults
The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and motor cable. This function is not a personnel
safety or a fire protection feature. See the firmware manual for more information.
■
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
76 Guidelines for planning the electrical installation
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...