North America: The local code (NEC) requires an overload protection and a
short-circuit protection for each motor circuit. Use, for example:
• a manual motor protector
• circuit breaker, contactor and overload relay or
• fuses, contactor and overload relay.
■
Protecting the motor against thermal overload
According to regulations, the motor must be protected against thermal overload and the
current must be switched off when overload is detected. The drive includes a motor
thermal protection function that protects the motor and switches off the current when
necessary. Depending on a drive parameter value, the function either monitors a
calculated temperature value (based on a motor thermal model) or an actual temperature
indication given by motor temperature sensors.
The motor thermal protection model supports thermal memory retention and speed
sensitivity. The user can tune the thermal model further by feeding in additional motor
and load data.
The most common temperature sensor types are PTC or Pt100.
For more information, see the firmware manual.
■
Protecting the motor against overload without thermal model or
temperature sensors
Motor overload protection protects the motor against overload without using motor
thermal model or temperature sensors.
Motor overload protection is required and specified by multiple standards including the
US National Electric Code (NEC) and the common UL/IEC 61800-5-1 standard in
conjunction with UL/IEC 60947-4-1. The standards allow for motor overload protection
without external temperature sensors.
The protection feature allows the user to specify the class of operation in the same
manner as the overload relays are specified in standards UL/IEC 60947-4-1 and
NEMA ICS 2.
The motor overload protection supports thermal memory retention and speed sensitivity.
For more information, see drive firmware manual.
74 Guidelines for planning the electrical installation
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...