Insulation jacket
1
Helix of copper tape or copper wire
2
Copper wire shield
3
Inner insulation
4
Cable core
5
Selecting the control cables
■
Shielding
Only use shielded control cables.
Use a double-shielded twisted pair cable for analog signals. This type of cable is
recommended for the pulse encoder signals also. Use one individually shielded pair for
each signal. Do not use common return for different analog signals.
A double-shielded cable (a) is the best alternative for low-voltage digital signals, but
single-shielded (b) twisted pair cable is also acceptable.
a
b
■
Signals in separate cables
Run analog and digital signals in separate, shielded cables. Do not mix 24 V DC and
115/230 V AC signals in the same cable.
■
Signals that can be run in the same cable
If their voltage does not exceed 48 V, relay-controlled signals can be run in the same cables
as digital input signals. The relay-controlled signals should be run as twisted pairs.
■
Relay cable
The cable type with braided metallic shield (for example ÖLFLEX by LAPPKABEL, Germany)
has been tested and approved by ABB.
■
Control panel to drive cable
Use EIA-485 with male RJ-45 connector, cable type Cat 5e or better. The maximum permitted
length of the cable is 100 m (328 ft).
74 Guidelines for planning the electrical installation
Summary of Contents for ACS880-07LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 07LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...16 Resistor braking Further information 12 Table of contents ...
Page 22: ...22 ...
Page 63: ...Mechanical installation 63 10 ...
Page 64: ...64 ...
Page 91: ...a b c 4 a 8 b 16 18 PE PE 10 13 12 Electrical installation 91 11 ...
Page 100: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 100 Electrical installation ...
Page 104: ...104 ...
Page 118: ...118 ...
Page 124: ...124 ...
Page 138: ...8 9 138 Maintenance ...
Page 139: ...11 12 12 6 10 Maintenance 139 ...
Page 150: ...150 ...
Page 160: ...160 ...
Page 183: ...Technical data 183 ...
Page 184: ...184 Technical data ...
Page 189: ... Dimension drawing examples ACS880 07LC 0850A 7 Dimensions 189 ...
Page 190: ...ACS880 07LC 1660A 7 6 pulse 190 Dimensions ...
Page 191: ...ACS880 07LC 1660A 7 A004 12 pulse Dimensions 191 ...
Page 192: ...ACS880 07LC 3260A 7 192 Dimensions ...
Page 195: ... 600 mm with main breaker double busbar bottom cable entry Dimensions 195 ...
Page 197: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 197 ...
Page 198: ...Inverter module cubicle with three R8i modules bottom cable exit 198 Dimensions ...
Page 199: ...Brake chopper cubicle Dimensions 199 ...
Page 200: ...200 ...
Page 216: ... Declaration of conformity 216 The Safe torque off function ...
Page 217: ...The Safe torque off function 217 ...
Page 218: ...218 ...
Page 220: ...220 ...