Mechanical installation 41
4
Mechanical installation
Contents of this chapter
This chapter describes the mechanical installation procedure of the drive.
Examining the installation site
Examine the installation site:
•
The installation site is sufficiently ventilated or cooled to transfer away the drive
losses.
1)
•
The ambient conditions of the drive meet the specifications.
1)
•
The wall behind the unit is of non-flammable material.
•
There is enough free space above the drive to enable cooling air flow, service and
maintenance.
•
The floor that the unit is installed on is of non-flammable material, as smooth as
possible, and strong enough to support the weight of the unit. Check the floor flatness
with a spirit level. The maximum allowed deviation from the surface level is 5 mm
(0.2 in) in every 3 meters (10 ft). Level the installation site, if necessary, as the cabinet
is not equipped with adjustable feet.
1)
The heat losses and ambient conditions are specified in chapter
.
Summary of Contents for ACS880-07C
Page 1: ... ABB INDUSTRIAL DRIVES Hardware manual ACS880 07C drives 45 to 710 kW 50 to 700 hp ...
Page 4: ......
Page 12: ...12 ...
Page 74: ...74 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Page 88: ...88 Electrical installation ...
Page 98: ...98 Control unit of frames R6 to R9 ...
Page 110: ...110 Fault tracing ...
Page 125: ...Maintenance 125 7 Install the sliding rail ...
Page 132: ...132 Maintenance 9 Fasten the extraction ramp to the cabinet base with two screws 9b 9a ...
Page 136: ...136 Maintenance ...
Page 148: ...148 Technical data R6 Input and output cable terminal size incoming switch OT160 ...
Page 149: ...Technical data 149 R7 Input and output cable terminal size incoming switch OT160 OT250 ...
Page 150: ...150 Technical data R8 Input and output cable terminal size incoming switch OT160 OT250 ...
Page 151: ...Technical data 151 R7 Input and output cable terminal size incoming switch OT315 ...
Page 152: ...152 Technical data R8 Input and output cable terminal size incoming switch OT315 ...
Page 153: ...Technical data 153 R9 Input and output cable terminal size incoming switch OT315 OT400 ...
Page 154: ...154 Technical data R9 Input and output cable terminal size incoming switch OT630 ...
Page 155: ...Technical data 155 R6 R7 R8 Input cable terminal size incoming switch OT160 OT250 option F250 ...
Page 156: ...156 Technical data R7 R8 Input cable terminal size incoming switch OT315 option F250 ...
Page 157: ...Technical data 157 R9 Input cable terminal size incoming switch OT315 OT400 option F250 ...
Page 158: ...158 Technical data R9 Input cable terminal size incoming switch OT630 option F250 ...
Page 159: ...Technical data 159 R6 R7 R8 Output cable terminal size DU DT filter option E205 ...
Page 160: ...160 Technical data R9 Output cable terminal size DU DT filter option E205 ...
Page 161: ...Technical data 161 R10 Input and output cable terminal size ...
Page 162: ...162 Technical data ...
Page 163: ...Technical data 163 ...
Page 164: ...164 Technical data R11 Input and output cable terminal size ...
Page 165: ...Technical data 165 ...
Page 166: ...166 Technical data ...
Page 172: ...172 Technical data ...
Page 174: ...174 Dimension drawings Frame sizes R6 to R8 ...
Page 175: ...Dimension drawings 175 Frame size R9 ...
Page 176: ...176 Dimension drawings Frame size R10 ...
Page 177: ...Dimension drawings 177 Frame size R11 ...
Page 178: ...178 Dimension drawings ...
Page 180: ...180 Safe torque off function ...