Grounding the outer shields of the control cables at the cabinet lead-through
Ground the outer shields of all control cables 360 degrees at the EMI conductive cushions
as follows:
1.
Loosen the tightening screws of the EMI conductive cushions and pull the cushions
apart.
2.
Cut adequate holes to the rubber grommets in the lead-through plate and lead the
cables through the grommets and the cushions into the cabinet.
3.
Strip off the cable plastic sheath above the lead-through plate just enough to ensure
proper connection of the bare shield and the EMI conductive cushions.
4.
Tighten the two tightening screws so that the EMI conductive cushions press tightly
round the bare shield.
View from above
Electrical installation 97
Connecting the control cables
See chapter
Control units of the drive
(page
127
) for the default I/O connections of the
inverter unit (with the ACS880 primary control program). The default I/O connections can
be different with some hardware options, see the circuit diagrams delivered with the drive
for the actual wiring. For other control programs, see their firmware manuals.
Control cable connection procedure
WARNING!
Obey the instructions in chapter
Safety instructions
. If you ignore
them, injury or death, or damage to the equipment can occur.
1.
Stop the drive (if running) and do the steps in section
Precautions before electrical
work
on page
19
before you start the work.
2.
Run the control cables into the auxiliary control cubicle (ACU) as described in section
Grounding the outer shields of the control cables at the cabinet lead-through
below.
3.
Route the control cables as described in section
Routing the control cables inside the
cabinet
(page
99
).
4.
Connect the control cables as described starting on page
99
.
Grounding the outer shields of the control cables at the cabinet lead-through
Ground the outer shields of all control cables 360 degrees at the EMI conductive cushions
as follows:
1.
Loosen the tightening screws of the EMI conductive cushions and pull the cushions
apart.
2.
Cut adequate holes to the rubber grommets in the lead-through plate and lead the
cables through the grommets and the cushions into the cabinet.
3.
Strip off the cable plastic sheath above the lead-through plate just enough to ensure
proper connection of the bare shield and the EMI conductive cushions.
4.
Tighten the two tightening screws so that the EMI conductive cushions press tightly
round the bare shield.
1
Tightening screw
2
EMI conductive cushion
3
Strain relief
4
Grommet
5
Lead-through plate
2
3
4
5
1
2
1
Electrical installation 97
Connecting the control cables
See chapter
Control units of the drive
(page
127
) for the default I/O connections of the
inverter unit (with the ACS880 primary control program). The default I/O connections can
be different with some hardware options, see the circuit diagrams delivered with the drive
for the actual wiring. For other control programs, see their firmware manuals.
Control cable connection procedure
WARNING!
Obey the instructions in chapter
Safety instructions
. If you ignore
them, injury or death, or damage to the equipment can occur.
1.
Stop the drive (if running) and do the steps in section
Precautions before electrical
work
on page
19
before you start the work.
2.
Run the control cables into the auxiliary control cubicle (ACU) as described in section
Grounding the outer shields of the control cables at the cabinet lead-through
below.
3.
Route the control cables as described in section
Routing the control cables inside the
cabinet
(page
99
).
4.
Connect the control cables as described starting on page
99
.
Grounding the outer shields of the control cables at the cabinet lead-through
Ground the outer shields of all control cables 360 degrees at the EMI conductive cushions
as follows:
1.
Loosen the tightening screws of the EMI conductive cushions and pull the cushions
apart.
2.
Cut adequate holes to the rubber grommets in the lead-through plate and lead the
cables through the grommets and the cushions into the cabinet.
3.
Strip off the cable plastic sheath above the lead-through plate just enough to ensure
proper connection of the bare shield and the EMI conductive cushions.
4.
Tighten the two tightening screws so that the EMI conductive cushions press tightly
round the bare shield.
View from above
1
Tightening screw
2
EMI conductive cushion
3
Strain relief
4
Grommet
5
Lead-through plate
2
3
4
5
1
2
1
Tightening screw
1
EMI conductive cushion
2
Strain relief
3
Grommet
4
Lead-through plate
5
Note 1:
Keep the shields continuous as close to the connection terminals as possible.
Secure the cables mechanically at the lead-through strain relief.
Note 2:
If the outer surface of the shield is non-conductive:
•
Cut the shield at the midpoint of the bare part. Be careful not to cut the conductors or
the grounding wire (if present).
•
Turn the shield inside out to expose its conductive surface.
•
Cover the turned shield and the stripped cable with copper foil to keep the shielding
continuous.
100 Electrical installation
Summary of Contents for ACS880-07
Page 1: ...ABB industrial drives Hardware manual ACS880 07 drives 560 to 2800 kW ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 94: ...94 ...
Page 112: ...Electrical installation 109 5 6 4 3 112 Electrical installation ...
Page 113: ...110 Electrical installation 7 8 8 Electrical installation 113 ...
Page 114: ...Electrical installation 111 9 10 114 Electrical installation ...
Page 116: ...Electrical installation 113 4 5 3 6 7 116 Electrical installation ...
Page 118: ...2 11 b PE 10 7 5 6 8 a 360 grounding detail 118 Electrical installation ...
Page 128: ...128 ...
Page 146: ...146 ...
Page 148: ...148 ...
Page 159: ...12 Install and tighten the two M4 12 T20 screws 10 11 12 Maintenance 159 ...
Page 162: ...6 6a 6a 6b 7a 7b 7 8 8a 8b 162 Maintenance ...
Page 166: ...166 Maintenance 6 6 7 8 7 166 Maintenance ...
Page 173: ...6 Reinstall the cover removed earlier and close the cubicle door 4 4 D7T D8T Maintenance 173 ...
Page 213: ... Dimension drawing examples Frame 2 D7T 2 R8i 12 pulse A004 Dimensions 213 ...
Page 214: ...Frame 1 D8T 2 R8i IP22 214 Dimensions ...
Page 215: ...Frame 1 D8T 2 R8i IP54 B055 Dimensions 215 ...
Page 216: ...Frame 1 D8T 2 R8i with common motor terminal cubicle H359 1 2 216 Dimensions ...
Page 217: ...Frame 1 D8T 2 R8i with common motor terminal cubicle H359 2 2 Dimensions 217 ...
Page 218: ...Frame 1 D8T 2 R8i with brake choppers and resistors D150 D151 1 2 218 Dimensions ...
Page 219: ...Frame 1 D8T 2 R8i with brake choppers and resistors D150 D151 2 2 Dimensions 219 ...
Page 220: ...Frame 1 D8T 2 R8i with sine output filter E206 1 2 220 Dimensions ...
Page 221: ...Frame 1 D8T 2 R8i with sine output filter E206 2 2 Dimensions 221 ...
Page 222: ...Frame 2 D8T 2 R8i 12 pulse A004 with grounding switch F259 222 Dimensions ...
Page 223: ...Frame 2 D8T 3 R8i 1 2 Dimensions 223 ...
Page 224: ...Frame 2 D8T 3 R8i 2 2 224 Dimensions ...
Page 225: ...Frame 2 D8T 3 R8i with common motor terminal cubicle H359 1 2 Dimensions 225 ...
Page 226: ...Frame 2 D8T 3 R8i with common motor terminal cubicle H359 2 2 226 Dimensions ...
Page 227: ...Frame 2 D8T 3 R8i with top entry top exit H351 H353 1 2 Dimensions 227 ...
Page 228: ...Frame 2 D8T 3 R8i with top entry top exit 2 2 228 Dimensions ...
Page 229: ...Frame 3 D8T 4 R8i 1 2 Dimensions 229 ...
Page 230: ...Frame 3 D8T 4 R8i 2 2 230 Dimensions ...
Page 231: ...Frame 3 D8T 4 R8i with common motor terminal cubicle H359 1 2 Dimensions 231 ...
Page 232: ...Frame 3 D8T 4 R8i with common motor terminal cubicle H359 2 2 232 Dimensions ...
Page 233: ...Frame 3 D8T 4 R8i with top entry top exit H351 H353 1 2 Dimensions 233 ...
Page 234: ...Frame 3 D8T 4 R8i with top entry top exit H351 H353 2 2 234 Dimensions ...
Page 235: ...Frame 4 D8T 5 R8i 6 pulse with top entry exit UL Listed C129 1 2 Dimensions 235 ...
Page 236: ...Frame 4 D8T 5 R8i 6 pulse with top entry exit UL Listed C129 2 2 236 Dimensions ...
Page 237: ... Dimensions of empty cubicles options C199 C200 C201 IP22 IP42 Dimensions 237 ...
Page 238: ...IP54 238 Dimensions ...
Page 243: ... 1000 mm UL CSA top cable entry Dimensions 243 ...
Page 244: ... 1000 mm UL CSA bottom cable entry 244 Dimensions ...
Page 264: ...264 ...
Page 272: ... 272 ...